Basic Documentation
43 / 44
Siemens VAV compact controller G..B181.1E/3 | VAV modular controller ASV181.1E/3 CE1P3544en
Smart Infrastructure 2021-10-26
9.2.6 Operating mode
The operating mode determines whether the setpoint signal (0…100 %) from the
supervisory controller is interpreted as volume flow control or as (air damper)
position control.
If used as damper control signal, the actual values from the flow sensor remain
available. This allows to implement the flow control loop in an external controller.
9.2.7 Restarting the device
Restarting is possible by a power-reset (switching operating voltage off and on).
Effect of restart: Device re-initializes and sets all process values to defaults.
Parameter values are not reset.