Basic Documentation

36 / 44
Siemens VAV compact controller G..B181.1E/3 | VAV modular controller ASV181.1E/3 CE1P3544en
Smart Infrastructure 2021-10-26
With regard to AC 24 V operating voltage, the following regulations must be
complied with:
Regulation
Operating
voltage
AC 24 V
The operating voltage must comply with the requirements for
SELV or PELV:
Permissible deviation of AC 24 V nominal voltage at the
actuators: +/–20 %
Specification
on AC 24 V
transformers
Safety isolating transformers as per EN 61558, with double
insulation, designed for 100 % on time to power SELV or
PELV circuits
Determine the transformer’s output by adding up the power
consumption in VA of all actuators used
For efficiency reasons, the power drawn from the transformer
should amount to at least 50 % of the nominal load
The transformer’s nominal capacity must be at least 25 VA.
With smaller transformers, the ratio of no-load voltage and full
load voltage becomes unfavorable (> + 20 %)
Fusing of
AC 24 V
operating
voltage
Secondary side of transformer:
According to the effective load of all connected devices
Line G (system potential) must always be fused
Where required, line G0 (system neutral) also
7.2 Device-specific regulations
Among other aspects, the safety of devices is ensured by extra low-voltage power
supply (AC 24 V) as per SELV or PELV.
Electrical parallel connection of VAV compact controllers provided the required
operating voltage tolerance is observed. The voltage drops of the supply lines
must be taken into consideration.
Mechanical coupling of the devices is not permitted.
Do not open the actuator!
The device is maintenance-free. Only the manufacturer may carry out any repair
work.
Operating voltage
AC 24 V
Device safety
Electrical parallel
connection
Warning,
maintenance