Technical data
Operating voltage / frequency
Power consumption GDB13..1 / GLB13..1 running
GDB16..1 / GLB16..1 running
holding
AC 24 V ± 20 % / 50/60 Hz
2 VA / 1 W
3 VA / 2 W
1 W
Nominal torque
Maximum torque (when blocked)
Nominal rotational angle / max. rotational angle
Running time for 90° rotational angle (GDB/GLB)
5 Nm (GDB) 10 Nm (GLB)
7 Nm (GDB) 19 Nm (GLB)
90° / 95° ± 2°
150 s (50 Hz) / 125 s (60 Hz)
Input voltage Y
Max. permissible input voltage
DC 0...10 V,
DC 35 V, internally limited to DC 10 V
Input voltage Y
Nonadjustable characteristics function
Adjustable characteristics function offset Uo
span ∆U
DC 0...35 V
DC 0...10 V
DC 0...5 V
DC 2...30 V
Output voltage U
Max. output current
DC 0...10 V
DC ± 1 mA
Degree of protection of housing as per EN 60 529 IP 20
Insulation class as per EN 60 730 III
Operation / transport
Temperature
Humidity (noncondensing)
IEC 721-3-3 / IEC 721-3-2
−32...+55 °C / −32...+70 °C
< 95% r. h. / < 95% r. h.
Product safety: Automatic electrical controls for household
and similar use
Electromagnetic compatibility (EMC):
Immunity
Emissions
Conformity: Electromagnetic compatibility
Low-voltage directive
Conformity: Australian EMC Framework
Radio Interference Emission Standard
EN 60 730-2-14
(type 1)
IEC/EN 61 000-6-2
IEC/EN 61 000-6-3
89/336/EEC
73/23/EEC
Radio Communication Act 1992
AS / NZS 3548
Actuator W x H x D (refer to "Dimensions")
Damper shaft: Round GDB
Round GLB
Round GLB
Square
Min. shaft length
Shaft hardness
70.7 x 156.2 x 60.6 mm
8...16 mm
8...10 mm with centering element
10...16 mm without centering element
6...12.8 mm
30 mm
< 300 AV
Post header AMP MTA 100/640456-6
Terminal strip Lumberg KRES03, max. 3 x 2.5 mm
2
Without packaging 0.48 kg
Disposal notes
The document “Technical basics” and the Environmental Product Declaration provide
information about environmental compatibility and disposal of the actuator.
Internal diagrams
GDB / GLB13..1J /
GDB / GLB13..1L
GDB / GLB16..1L GDB / GLB16..1J
AC 24 V
3-position control
AC 24 V
Modulating control
4628G01
Y2
AC 0 V
G
Y1
AC 24 V
M
G.B13...
100%
0%
G
DC 0...10 V
Y
G0
U
AC 24 V
SELV/PELV
M
G.B16..1L
4628G02
100%
0%
G
DC 0...10 V
Y
G0
AC 24 V
SELV/PELV
M
G.B16..1J
AC 24 V supply
(SELV / PELV)
Functional data
Positioning signal for
GDB16..1 /GLB16..1
Characteristics functions for
GDB/GLB161.1J+L
GDB/GLB163.1J+L
Position indicator for
GDB/GLB16..1L
Protection
Environmental conditions