Data Sheet for Product

8 / 14
Siemens A6V10881143_en--_e
Smart Infrastructure 2021-06-17
Notes
Safety
Caution
National safety regulations
Failure to comply with national safety regulations may result in personal injury and
property damage.
Observe national provisions and comply with the appropriate safety regulations.
Mounting
Do not open the rotary actuators
Mounting positions, cf. mounting instr. A6V10920701
1)
1)
Related documents such as environmental declarations, CE declarations, etc., can be
downloaded at the following internet address:
http://siemens.com/bt/download
Engineering
GDB..9E.. actuators may only be used at medium temperatures > 0 °C.
If condensation occurs at the mounting site, the use of the temperature adapter ALJ100 is
recommended in order to protect the actuator. If the medium temperature is ≤ 0 °C, the
adapter shaft must be greased with silicon grease.
T
M
Medium temperature
T
A
Ambient temperature
Range of use for actuator/valve
Use with ALJ100