Data Sheet for Product
4 / 14
Siemens A6V10881143_en--_e
Smart Infrastructure 2021-06-17
HMI (Human-Machine Interface)
For more detailed explanations on device states, functions and error display, cf. product
documentation CE1Z4634
1)
.
Push-button operation
Activity Push-button operation Confirmation
Display current address
(in reverse order)
Press button < 1s Current address is displayed
Enter Modbus address with push-button Press button > 1s and < 5s See description next page
Enter push-button addressing mode
(for use with Climatix
TM
controllers)
Press button > 5s and < 10s
LED shines orange (release
button when red LED gets
dark). Timeout after 1 min.
Reset to factory settings Press button > 10s LED flashes orange
LED colors and patterns
Color Pattern Description
Green steady Start-up
1s on / 5s off Fault free operation (“life pulse”)
flashing Bus traffic
Orange / green 1s orange / 1s green Device is in override control
Orange 1s on / 1 off Bus parameters not yet configured
Orange 1s on / 5s off Backup mode entered
Red Steady Mechanical fault / device jammed
1s on / 5s off Internal error
0.1s on / 1s off Invalid configuration, e.g. Min = Max
Resetting the device by push button
The rotary actuators can be reset by push-button:
1. Press button for >10s LED starts flashing orange
2. Release button while LED still flashes LED keeps flashing for 3s
3. If the button is pressed within these 3s, the reset is cancelled.
4. After those 3s LED shines red (reset), then green (start-up).
1)
Related documents such as environmental declarations, CE declarations, etc., can be
downloaded at the following Internet address:
http://siemens.com/bt/download