Data Sheet for Product

13 / 14
A6V10881143_en--_e Siemens
2021-06-17 Smart Infrastructure
Diagrams
Internal diagrams
The rotary actuators are supplied with a prewired connecting and communication cable. All
interconnected devices must be connected to the same G0.
Core
desig.
Core color
Terminal
code
Description
1 red (RD) G System voltage AC 24 V
2 black (BK) G0 System neutral AC 24 V
6 violet (VT) REF Reference
8 grey (GY) + Bus (Modbus RTU)
9
pink (PK) - Bus (Modbus RTU)
Note
The operating voltage at terminals G and G0 must comply with the requirements under
SELV or PELV. Safety transformers with twofold insulation as per EN 61558 required; they
must be designed to be on 100 % of the time.
Dimensions
Actuator
Dimensions in mm
= > 100 mm
 = >200 mm
Minimum clearance from ceiling or wall for mounting,
connection, operation, maintenance etc.