Data Sheet for Product
6 / 12
Siemens A6V10881141_en--_c
Smart Infrastructure 2019-04-25
Register 769 “Status”
Status
Bit 00 1 = Local override Bit 06 1 = Adaption done
Bit 01 1 = Backup mode active Bit 07 1 = Adaption in progress
Bit 02 1 = reserved Bit 08 1 = Adaption error
Bit 03 1 = reserved Bit 09 1 = Selftest failed
Bit 04 1 = Device jammed Bit 10 1 = Selftest passed
Bit 05 1 = Nom. lifetime exceeded Bit 11 1 = Invalid configuration
Supported function codes
Function codes
03 (0x03) Read Holding Registers
04 (0x04) Read Input Registers
06 (0x06) Write Single Register
16 (0x10) Write Multiple registers (Limitation: Max. 120 registers within one message)
Notes
Safety
Caution
National safety regulations
Failure to comply with national safety regulations may result in personal injury and
property damage.
● Observe national provisions and comply with the appropriate safety regulations.
Mounting
● Do not open the damper actuators
● Do not use the accessory mounting holes for fixation of the damper actuators
Mounting
Mounting positions
IP54 protection in following mounting positions Accessory mounting holes
1)
Cf. mounting instr. A6V10409478
2)
1)
Not to be used for fixation of the actuator, use anti-rotation-bracket instead.
2)
Related documents such as environmental declarations, CE declarations, etc., can be
downloaded at the following internet address:
http://siemens.com/bt/download