Data Sheet for Product
3 / 12
A6V10881141_en--_c Siemens
2019-04-25 Smart Infrastructure
HMI (Human-Machine Interface)
For more detailed explanations on device states, functions and error display, cf. product
documentation CE1Z4634
1)
.
Push-button operation
Activity Push-button operation Confirmation
Display current address
(in reverse order)
Press button < 1s Current address is displayed
Enter Modbus address with push-button Press button > 1s and < 5s See description next page
Enter push-button addressing mode
(for use with Climatix
TM
controllers)
Press button > 5s and < 10s LED shines orange (release
button when red LED gets
dark). Timeout after 1 min.
Reset to factory settings Press button > 10s LED flashes orange
LED colors and patterns
Color Pattern Description
Green steady Start-up
1s on / 5s off Fault free operation (“life pulse”)
flashing Bus traffic
Orange / green 1s orange / 1s green Device is in override control
Orange 1s on / 1 off Bus parameters not yet configured
Orange 1s on / 5s off Backup mode entered
Red Steady Mechanical fault / device jammed
1s on / 5s off Internal error
0.1s on / 1s off Invalid configuration, e.g. Min = Max
Resetting the device by push button
The damper actuators can be reset by push-button:
1. Press button for >10s à LED starts flashing orange
2. Release button while LED still flashes à LED keeps flashing for 3s
3. If the button is pressed within these 3s, the reset is cancelled.
4. After those 3s à LED shines red (reset), then green (start-up).