s OpenAir™ Communicative Damper Actuators KNX / PL-Link G..B111.1E/KN Damper actuators 5 / 10 Nm with KNX communication • • • • A6V11753386_en--_a 2020-02-25 GDB111.1E/KN with 5 Nm nominal torque GLB111.
Type summary Product no. Stock no. GDB111.1E/KN S55499-D190 GLB111.1E/KN S55499-D198 Operating voltage Positioning signal AC 24 V KNX-TP Power consumption 1 VA / 0,5 W 3 VA / 2,5 W 1) Positioning time Manual adjuster Position feedback 150 s Yes Yes Please refer to data sheet N4698 for information on accessories and spare parts. 1) Actuator rotates Ordering (Example) Product no. Stock no. Description Amount GDB111.
Notes Safety Caution National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage. • Observe national provisions and comply with the appropriate safety regulations. Mounting • Do not open the damper actuators. • Do not use the accessory mounting holes for fixation of the damper actuators. Instead use the shaft fixation screw and the enclosed anti-rotation-bracket.
HMI (Human-Machine Interface) Push-button operation Activity Push-button operation Confirmation Enter / leave addressing mode Press button <1 s LED turns red or turns off Reset to factory settings Press button >20 s LED flashes orange until device restarts Press key >2 s and <20 s LED flashes orange 1x PL-Link connection test 4) LED colors and patterns Color Pattern Description Off --- Fault free operation or device not powered Green steady Connection test successful Orange flashing
Commissioning and parameterization The following parameters are checked or set during engineering and commissioning in the ETS engineering tool. Parameter Range Description Factory settings Adaption of actual (if mechanically limited) opening range to position feedback 0...100% Off Tab card “standard” Adaptive positioning On / Off Off = No adaption / On = Adaption active Backup timeout 0..60 min 0 min = disabled Time interval to detect communication interruption. 30 min.
KNX Group Objects No. Name in ETS Object function Flags C R W T U ID Data point type KNX DPT_Name Format Unit Range 1 Fault information Transmit 1 1 0 1 0 219.001 _AlarmInfo 6 Byte --- cf. Description below 2 Fault state Transmit 1 1 0 1 0 1.005 _Alarm 1 bit --- 0 = No alarm 1 = Alarm 3 Fault transmission Receive 1 0 1 0 1 1.003 _Enable 1 bit --- 0 = Disable 1 = Enable 4 Setpoint Receive 1 1 1 0 1 5.
Description of Group Objects 1 Fault information If group object #3 ”fault transmission” is set to “on”, the following faults can be transmitted if they occur. In that case, group object #2 value changes to “alarm”. Error Group obj. #1 Description Resolution Device jammed XX 00 0A 03 0C 05 Target position cannot be reached due to mechanical blockage. Remove blockage (visual inspection required). Or invert Opening direction, if it is set wrongly.
Technical data Power supply Operating voltage G..B111.1E/.. AC 24 V ± 20 % (SELV) or AC 24 V class 2 (US) Frequency Power consumption 50/60 Hz at 50 Hz Actuator holds 1 VA / 0.5 W Actuator rotates 3 VA / 2.5 W Function data Positioning time for nominal rotation angle G..B111.1E/.. Nominal torque GDB.. 5 Nm GLB.. 10 Nm GDB.. < 7 Nm GLB..
Directives and Standards Product standard EN60730-x Electromagnetic compatibility (Application) For residential, commercial and industrial environments GDB111.1E/KN GLB111.1E/KN EU Conformity (CE) A5W00003842 1) A5W00000176 1) RCM Conformity A5W00003843 1) A5W00000177 1) UL, cUL AC 24 V UL 873 http://ul.
Dimensions Measurements in mm Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a 6300 Zug Switzerland Tel. +41 58-724 24 24 www.siemens.com/buildingtechnologies Document ID A6V11753386_en--_a Edition 2020-02-25 © Siemens Switzerland Ltd, 2020 Technical specifications and availability subject to change without notice.