User Manual
4 / 10
Siemens A6V10636149_en--_b
Building Technologies 2016-12-14
Engineering
Potentiometer and auxiliary switches
Potentiometer and auxiliary switches cannot be added in the field
Installation
WARNING
No internal line protection for supply lines to external consumers
Risk of fire and injury due to short-circuits
● Adapt the line diameters as per local regulations to the rated value of the installed fuse.
Maintenance
The actuators GDB..1E are maintenance-free.
Disposal
The device is considered an electronics device for disposal in terms of Eu-
ropean Directive 2012/19/EU and may not be disposed of as domestic gar-
bage.
● Dispose of the device through channels provided for this purpose.
● Comply with all local and currently applicable laws and regulations..
Technical data
Power supply (GDB1..1E)
Operating voltage (SELV/PELV) / Frequency AC 24 V ~ ±20 % (19.2…28.8 V ~) / 50/60 Hz
DC 24…48 V ⎓ ±20 % (19.2…57.6 V ⎓)
1)
Power consumption running GDB14..1E,
GDB16..1E
2 VA / 1 W
2.1 VA / 1.2 W
Power consumption holding GDB14..1E,
GDB16..1E
0.5 W
0.7 W
Power supply (GDB3..1E)
Operating voltage / Frequency AC 100…240 V ~ ±10 % (90…264 V ~) / 50/60 Hz
Power consumption running GDB34..1E,
GDB36..1E
5 VA / 1.6 W
3.3 VA / 1.2 W
Power consumption holding GDB34..1E,
GDB36..1E
0.9 W
0.5 W
Function data
Nominal torque
Maximum torque (blocked)
Minimum holding torque
5 Nm
10 Nm
5 Nm
Nominal rotary angle (with position indication)
Maximum rotary angle (mechanic limitation)
90°
95° ± 2°
Runtime for 90° rotary angle 150 s
Actuator sound power level 28 dB(A)
1)
C-UL: Permitted only to DC 30 V ⎓