User Manual

6
Siemens A6V11997021_en--_a
Smart Infrastructure 2020-06-09
Environmental conditions
Operation
Climatic conditions
Mounting location
Temperature extended
Humidity (non-condensing)
IEC 60721-3-3
Class 3K5
interior, weather-protected
- 32…+ 55°C
< 95 % r.h.
Transport
Climatic conditions
Temperature extended
Humidity (non-condensing)
IEC 60721-3-2
Class 2K3
- 32…+ 70°C
< 95 % r.h.
Storage
Climatic conditions
Temperature extended
Humidity (non-condensing)
IEC 60721-3-1
Class 1K3
- 32…+ 50°C
< 95 % r.h.
Mechanical conditions
Class 2M2
Standards, directives and approvals
Product standard
EN 60730
Part 2-14 / Particular requirements for electric
actuators
Electromagnetic compatibility
(Applications)
For use in residential, commercial, light-industrial
and industrial environments
EU Conformity (CE)
GDA141.1E, GDA146.1E, GDA161.1E
GLA141.1E, GLA146.1E, GLA161.1E
A5W00026943
A5W00026945
RCM
GDA141.1E, GDA146.1E, GDA161.1E
GLA141.1E, GLA146.1E, GLA161.1E
A5W00026947
A5W00026949
EAC
Eurasian conformity
Environmental compatibility
The product environmental declaration (A5W00026066) contains data on environmentally compatible product
design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).
Dimensions
Actuator W x H x D
See “Dimensions” P8
Damper shaft
round
round
Square
Min. shaft length
Shaft hardness
8…16 mm
8…10 mm (with centering element)
6…12.8 mm
20 mm
< 300 HV
Weight
Without packaging
Max. 0.49 kg, without switches
Max. 0.63 kg, with switches
* The documents can be downloaded from http://siemens.com/bt/download.








