Basic Documentation

36/44
Siemens Rotary actuators with spring return GCA…1 CE1Z4613en
Building Technologies Technic al data 2017-05-26
Protected against faulty wiring max. AC 24 V / DC 24…48 V
Output signal (wires 9-2)
Output voltage U
Max. output current
Protected against faulty wiring
DC 0...10 V
DC ° 1 mA
max. AC 24 V / DC 24…48 V
Change of resistance (wires P1-P2)
Load
Max. sliding contact current
Permissible voltage at potentiometer (SELV/PELV)
Insulation resistance between potentiometer and housing
0...1000 ς
< 1 W
< 10 mA
AC 24 V / DC 24…48 V
AC 500 V
AC power supply
Switching voltage
Nominal current res./ind.
Life: 6 A res., 2 A ind.
without load
DC power supply
Switching voltage
Nominal current
Electric strength auxiliary switch against housing
Switching range for auxiliary switches
Setting increments
Switching hysteresis
Factory switch setting
Switch A
Switch B
AC 24...230 V
6 A / 2 A
10
4
cycles
10
6
cycles
DC 12..30 V
DC 2 A
AC 4 kV
5°...90°
85°
Cross-sectional area of prewired connecting cables
Standard cable length
Permissible length for signal lines (non-communicative types)
0.75 mm
2
0.9 m
300 m (see chapter 6)
Degree of protection as per EN 60 529 IP 54
Insulation class
AC 24 V / DC 24…48 V
AC 230 V
Feedback potentiometer
Auxiliary switch
as per EN 60 730
lll
II
lll
II
Operation
Climatic conditions
Mounting location
Temperature
Humidity (noncondensing)
Transport
Climatic conditions
Temperature
Humidity (noncondensing)
Mechanical conditions
IEC 721-3-3
class 3K5
interior, weather-protected
,32....+55 °C
< 95 % r.h.
IEC 721-3-2
class 2K2
,32...+70 °C
< 95 % r.h.
class 2M3
Product safety
Automatic electrical controls
for household and similar use
Electromagnetic compatibility
(Application)
EU Conformity (CE)
RCM Conformity
EN 60 730-2-14
(Type 1)
For residential, commercial and
industrial environments
A5W00004370
1)
A5W00004371
1)
EAC Conformity
Eurasia conformity for all
GCA.. variants
UL, cUL
UL 873 http://ul.com/database
Product environmental declaration
2)
CE1E4613en
1)
and
A6V101083254en
1)
Actuator W x H x D (see "Dimensions")
Damper shaft
Round
Square
Min. length
Max. shaft hardness
100 x 300 x 67.5 mm
8...25.6 mm
6...18 mm
20 mm
< 400 HV
Outputs
Position indicator
for GCA16..1
Feedback potentiometer
for GCA135.1
Auxiliary switch
for GCA..6.1, GCA164.1
Connecting cables
Degree of protection of housing
Protection class
Environmental conditions
Standards and directives
Dimensions