Specifications
Ambient
Conditions
Ambient temperature
operation -25°F to 130°F (-32°C to 55°C)
storage and transport -40°F to 158°F (-40°C to 70°C)
Ambient humidity (non-condensing) 95% rh
Agency
Certification
Conformity
UL listed to UL60730
(to replace UL873)
cUL certified to Canadian Standard
C22.2 No. 24-93
Electromagnetic compatibility (EMC) 2004/108/EC
Immunity for all models, except GCA132.xx EN61000-6-2
Immunity for GCA132.xx EN61000-6-1
Emissions for all models EN61000-6-3
Power
Supply
GCA16x GCA15x GCA13x GCA12x GCA22x
24 Vac ± 20%
24 Vdc ± 10%
24 Vac ± 20%
24 Vdc ± 10%
24 Vac± 20%
24 Vdc ± 10%
24 Vac ±
20%
24 Vdc ±
10%
120 Vac ±
10%
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
Power Consumption
running
7 VA/5W 7 VA/5W 7 VA/5W 7 VA/5W 8 VA
holding
5 VA/3W
5 VA/3W
5 VA/3W
5 VA/3W
6 VA
Control Signal
GCA16x
GCA15x
GCA13x
GCA12x
GCA22x
Input Signal
(YG0)
voltage input
0 to 10 Vdc
(max. 35 Vdc)
0 to 10 Vdc or
2 to 10 Vdc
(max. 35 Vdc)
Floating
2-Position
2-Position
input resistance
>100K ohms
>100K ohms
Feedback
Signal
GCA16x
GCA15x
GCA13x
GCA12X
GCA22x
Position output signal
(U-G0)
voltage output
0 to 10 Vdc
0 to 10 Vdc
0 to 1000 ohms
<10 Ma
(GCA 132x only)
Load <1W
maximum output
current
±1 mA
+1 mA,
-.5 mA
Function
Running/spring return torque
Operating with 24 Vac 160 lb-in (18 Nm)
Maximum torque <360 lb-in (40 Nm)
Runtime for 90°
operating with motor 90 sec
closing (on power loss) with spring return 15 seconds typical
NOTE: At -25°F, spring return is 142 lb-in (16 Nm
).
Equipment rating
Class 2, in accordance with UL/CSA