Data Sheet for Product

OpenAir™ GCA Series, Spring Return,160 lb-in, Electronic Damper Actuator Submittal Sheet
Document No. 154-001P25
August 28, 2012
Technical Data
24 Vac, 120 Vac Torque: 160 lb-in (18 Nm) running and spring
return
<360 lb-in (40 Nm) maximum
NOTE:
At -25°F, spring return is 142 lb-in (16 Nm)
Runtime for 90°: 90 sec. operating,
15 sec. typical (30 sec. max.) closing on
power loss
Frequency: 50/60 Hz
Power consumption: 7 VA/5W (24 Vac/dc; GCA12x, GCA13x)
Running: 7 VA/5W (24 Vac/dc, GCA15x)
7 VA/5W (24 Vac/dc GCA16x)
8 VA (120 Vac GCA22x)
Power consumption:
Holding 5 VA/3W (24 Vac/dc, GCA12x)
5 VA/3W (24 Vac/dc, GCA13x, GCA15x)
5 VA (24 Vac/dc, GCA16x)
6 VA (120 Vac, GCA22x)
Equipment rating (24V): Class 2 per UL/CSA
Noise level: <45 dBA (running)
Angle of rotation: 90° nominal, 95° max.
Shaft dimensions: 3/8-in to 1-in (8 to 25.6 mm) dia.
1/4-in to 3/4-in (6 to 18 mm) sq.
3/4-in (20 mm) min. length
Operating temperature: -25°F to 130°F (-32°C to 55°C)
Storage temperature: -40°F to 158°F (-40°C to 70°C)
Ambient humidity: 95% rh (non-condensing)
Pre-cabled connection: 18 AWG, 3 ft (0.9 m) long
Enclosure: NEMA 2, IP54 per EN 60 529
Material: Die cast aluminum alloy
Agency listings: CE, UL60730, cUL C22.2 No. 24-93
Gear Lubrication: Silicone-free
Weight: 4.85 lb (2.2 kg)
Dimensions: 11-13/16 in (300 mm) H
4-3/4 in (120 mm) W
2-7/8 in (72 mm) D
Typical Specifications
Spring return damper actuators shall be the type that requires no
connecting linkages. The spring return actuators shall have a self-
centering damper shaft coupling that assures concentric alignment of
the actuator’s output coupling with the damper shaft and be capable of
direct mounting to a shaft up to a 1-inch diameter. Actuators shall use a
brushless DC motor and provide stall protection throughout the full
range of rotation. All spring return actuators shall be capable of both
clockwise and counterclockwise spring return fail-safe operation using a
continuously engaged mechanical return spring that returns the actuator
to a fail-safe position in <20 seconds in response to a loss of power. All
actuators shall provide a means of manually positioning the output
coupling in the absence of power. Dual independently adjustable
auxiliary switches must be integral to the actuator. All actuators must be
precabled and provide an easily readable high contrast yellow on black
position indicator. All actuators shall be UL60730 and CSA22.2 listed
and manufactured under ISO 9002 and ISO 14000 procedures.
Actuators shall be designed for a minimum of 60,000 full stroke cycles
at the actuators rated torque and temperatures. Actuators shall be as
manufactured by Siemens Industry, Inc.
Wiring Diagrams
2-Position, 24 Vac/dc:
M
SWITCH
A
SWITCH
B
DUAL AUXILIARY
SWITCHES
S1
S4
S2 S3 S5 S6
2
1
EA0864R1
NEUTRAL N.C. N.O. N.C. N.O.
COMMON
SUPPLY
COMMON
Floating, 24 Vac/dc:
M
1000
0% 100%
OPTIONAL
POTENTIOMETER
CONTROL SIGNAL
P1 P2 P3
DUAL AUXILIARY
SWITCHES
COMMON
S1
COMMON
S4
S2
N.C.
Switch
A
S3
N.O.
S5
N.C.
Switch
B
S6
N.O.
1
SUPPLY
CW
6
CCW
7
2
NEUTRAL
EA1103R2
0 to 10 Vdc, GCA16x, 24 Vac/dc;
2 to 10 Vdc, GCA15x, 24 Vac/dc:
SWITCH
A
SWITCH
B
DUAL AUXILIARY
SWITCHES
S1
S4
S2 S3 S5 S6
EA0867R1
N.C. N.O. N.C. N.O.
COMMON COMMON
M
NEUTRALSUPPLY
OUTPUTINPUT
1
8
9
2
2-Position, 120 Vac:
M
SWITCH
A
SWITCH
B
DUAL AUXILIARY
SWITCHES
S1
S4
S2 S3 S5 S6
4
3
EA0955R1
NEUTRAL N.C. N.O. N.C. N.O.
COMMON
LINE
COMMON
.
Information in this publication is based on current specifications. The company reserves the right to make changes as design improvements are
introduced. OpenAir is a trademark of Siemens Schweiz AG. Product or company names mentioned herein may be the trademarks of their
respective owners. © 2012 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089
USA
+ 1 847-215-1000
Your feedback is important to us. If you have comments about
this document, please send them to
sbt_technical.editor.us.sbt@siemens.com
Document No. 154-001P25
Printed in the USA
Page 2 of 2