Data Sheet for Product

5/6
Siemens Air damper actuators GBB/GIB..1, Rotary version CM2N4626E
Smart Infrastructure 2019-11-28
Disposal
The device is considered an electronics device for disposal in terms of
European Directive 2012/19/EU and may not be disposed of as domestic
garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regula-
tions.
Internal diagrams
GBB/GIB13..1 / GBB/GIB33..1 GBB/GIB16..1
Three-position control Modulating control
4626G01
A
100%
0%
(Y2)
AC 0 V
0...1000
W
AC 24 V...230 V / 6 (2) A
(a)
(G)
(Q12)
(Q14)
(Q24)
(Q22)
1
S2 S3 S5 S6
7 P3 S1 S4
(Q11)
(Q21)
B
(Y1)
(b)
(c)
6 P1
P2
AC 24 V
M
SELV/PELV
GBB/GIB13...
4626G02
A
100%
0%
(Y2)
AC 230 V
0...1000 W
AC 24 V...230 V / 6 (2) A
(a)
(N)
(Q12)
(Q14)
(Q24)
(Q22)
4
S2 S3 S5 S6
7 P3 S1 S4
(Q11)
(Q21)
B
(Y1)
(b)
(c)
6 P1 P2
M
SELV/PELV
GBB/GIB33...
DC 0...10 V / 0...35 V
4626G03
A
100%
0%
DC 0..10 V
(G)
AC 24 V
DC 0..10 V
GIB16...
(Y)
(G0)
(U)
(Q12)
(Q14)
(Q24)
(Q22)
2 9
S2 S3 S5 S6
1 8 S1 S4
(Q11)
(Q21)
B
AC 24 V...230 V / 6 (2) A
GBB16...
SELV/PELV
M
Pin
Cable
Meaning
Code No. Color Abbreviation
Actuators G 1 red RD System potential AC 24 V
AC 24 V G0 2 black BK System neutral
Y1 6 purple VT Position signal AC 0 V, clockwise
Y2 7 orange OG Position signal AC 0 V, counter-clockwise
Y 8 grey GY Position signal DC 0...10 V, 0...35 V
U 9 pink PK Position indication DC 0...10 V
Actuators N 4 blue BU Neutral conductor
AC 230V Y1 6 black BK Control signal AC 230 V, clockwise
Y2 7 white WH Control signal AC 230 V, counter-clockwise
Auxiliary switch Q11 S1 grey/red GY RD Switch A Input
Q12 S2 grey/blue GY BU Switch A Normally closed contact
Q14 S3 grey/pink GY PK Switch A Normally open contact
Q21 S4 black/red BK RD Switch B Input
Q22 S5 black /blue BK BU Switch B Normally closed contact
Q24 S6 black /pink BK PK Switch B Normally open contact
Feedback a P1 white/red WH RD Potentiometer 0...100 % (P1-P2)
potentiometer b P2 white/blue WH BU Potentiometer pick-off
c P3 white/pink WH PK Potentiometer 100...0 % (P3-P2)
Cable labeling