OpenAirä Rotary actuators without spring return GBB/GIB..1 Technical basics Edition 2.
/44 Siemens Smart Infrastructure Rotary actuators without spring return GBB/GIB..
Contents 1 Introduction ................................................................................................... 5 1.1 Revision history............................................................................................. 5 1.2 About this document ..................................................................................... 5 1.3 Document contents ....................................................................................... 6 2 Non-spring return actuators .......
7.3.1 HMI – Human-machine interface ................................................................29 7.3.2 Push button addressing ..............................................................................30 7.3.3 Commissioning ............................................................................................31 7.3.4 Modbus registers .........................................................................................32 7.3.5 Parameter and function description ...................
1 Introduction 1.1 Revision history Changes Powerpack Setting and operating elements Mechanical parallel connection of two actuators Electrical parallel connection of actuators Determining the actuator type Position indicator Technical data (power supply / torque) Internal diagram GBB/GIB16..1 Dimensions Accessories (ASC77..
1.3 Document contents This document contains basic technical information on type series GBB/GIB...
2 Introduction Non-spring return actuators This chapter provides information on application, functions, and equipment combinations. Furthermore, it contains a type summary and explains the actuator design including setting and operating elements for this family of actuators. 2.1 Application The actuators are used in ventilation and air conditioning plants to operate air dampers and air throttles: · · · · For damper areas up to 4 m2, friction-dependent Suitable for modulating controllers (DC 0...
2.2 Type summary The following table shows the options for the actuator types. GBB/GIB.. 131.1E 135.1E Mode of control Operating voltage AC 24 V 136.1E 331.1E 335.1E 336.1E 161.1E Three-position (see section 2.1 “Application”) X X X X 164.1E 166.1E Modulating control X Operating voltage AC 230 V 163.1E X X X 161.1E/MO Modbus RTU X X X Positioning signal input Y DC 0...10 V X DC 0...35 V with characteristic function X X X Modbus RTU X Position indicator U = DC 0...
2.3 Description of functions 2.3.1 Description of functions for GBB/GIB..1 The functions are listed in a table and are assigned to the respective modes of control. Type Mode of control GBB/GIB13..1 / GBB/GIB33..1 GBB/GIB16..1 GIB161.1E/MO Three-position Modulating Modbus RTU (see section 2.1 “Application”) Positioning signal with adjustable characteristic Y = DC 0...35 V with - function offset Uo = 0...5 V and span DU = 2...
2.3.2 Supplementary information on the description of functions for GBB/GIB16..1 Supplement The following information applies to modulating actuators. Characteristic function (GBB/GIB163.1, GBB/GIB164.1) Offset Uo and span DU can be adjusted using two potentiometers (see section 3.4 "Adjustable characteristic function"). The maximum permissible input voltage (Uo + DU) is DC 35 V.
2.5 Mechanical design Brief description The electromotoric GBB/GIB..1 actuators are available for three-position and modulating control, GIB161.1E/MO electronic actuators are available for networked control. The maximum torque is 20/35 Nm. The actuator's connecting cables are prewired. Housing Robust, light-weight full metal housing made of die-cast aluminium. The housing guarantees a long actuator life even under harsh environmental conditions.
2.6 Setting and operating elements Actuator Legend 12 11 1 2 90° A B PUSH 3 0 Uo 1 5 4 4 4626Z05 10 9 8 7 8 9,10 DU 2 5 10 15 30 25 5 1 2 3 4 5 6 20 11 12 13 14 15 2 3 16 16 15 6 Housing Rotary angle scale 0°...
3 Technical design This chapter discusses the following topics: · Drive motor · Adjustable auxiliary switches · Adjustable characteristic function (positioning signal, DC 0...35 V) · Control characteristics by including the neutral zone Introduction 3.1 Drive motor A synchronous motor enables accurate speed control. The magnetic clutch serves as a torque supervision to protect both actuator and damper. Drive motor 3.
3.3 Electrical functions Auxiliary switches and positioning signals The illustration below shows the relationship between the angular rotation, the adjustable switching points for auxiliary switches A and B and the positioning signal.
3.4 A modulating positioning signal DC 0..35 V from a controller drives the actuator. The angular rotation is proportional to the positioning signal. Using potentiometer "Uo", you can set the offset for DC 0...5 V, and with potentiometer "DU", you can set the span for DC 2...30 V. Ys [%] 100 4) 1) 3) 2) 4637D04 Actuators GBB/GIB163.1, GBB/GIB164.1 Adjustable characteristic function DU 5 2 10 15 20 30 25 Uo 0 0 2 2 5 30 10 35 Y [V] 3 5 DU (max.
Y S [%] 100 4637D02 Characteristic function for the example Max. positioning range Ysmax = Span Ys = Offset Uo = Span DU = 50 0 2 Uo U min 3.5 10 18 100 % (95°) 50 % (47.5°) 2V 16 V Y [V] Effective span DUw = Umax – Umin = 10 V - 2 V = 8 V DU (16 V) U max Neutral zone Actuators GBB/GIB16..1 (DC 0...10 V) For modulating actuators, note the control characteristic for the selected switch-on point of the setpoint.
4 Engineering notes Introduction Carefully study the basics of the control systems used before proceeding to the sections below, and pay special attention to all safety-related information. Intended use Use these actuators in a system only for applications as described in the basic system documentation of the control systems used. Additionally, note the actuator-specific properties and conditions as described in this chapter and in chapter 8 Technical data. 4.
Operating voltage AC 24 V, AC 230 V The following regulations apply to these operating voltages: Operating voltage AC 24 V Operating voltage AC 230 V Specification on AC 24 V transformers Fuse of AC 24 V operating voltage Transformers, secondary side: · According to the effective load of all connected devices · Line G (system potential) must always be fused.
Electrical parallel connection of actuators Same device types with index A can be electrical parallel wired. Same device types with index B (or higher) can also be electrical parallel wired. Mix of electrical parallel wiring of device types with index A and B (or higher) is not possible. Up to 10 actuators of the same device type can be electrical parallel wired. Cable length and cable cross section have to be respected. See chapter 6 “Wiring notes” for more information.
The following chart (example EMCO) allows for determining the total torque for this air damper type. 6 3 675 2 Damper height H [mm] 1 400 600 ta l 1005 To 4 pr 13 35 5 0 200 es su r e [P ] 16 65 7 4621D01en 19 95 8 20 00 100 9 0 0 Friction torque (excl.
5 Mounting notes Mounting instructions All information and steps to properly prepare and mount the actuator are available in the mounting instructions 4 319 2685 0 (M4626) delivered with the actuator. The shaft adapter as well as all other individual parts are not premounted, as the actuator components are put together differently depending on damper shaft length. Refer to section 2.5 “Mechanical design".
6 Introduction Wiring notes Prior to wiring, study all information in the following sections: · "Safety notes" in section 4.1 · "Device-specific regulations" in section 4.2 · "Notes on EMC optimization" in section 4.3 · "Connection Diagrams" in chapter 9, and the · HVAC plant diagram. 6.1 Permissible line lengths and cross sectional area The permissible line lengths and cross-sectional areas depend on the actuators’ power consumption and the voltage drop of the connection lines to the controller.
Line length/ consumption AC 24 V The diagram applies to AC 24 V and shows the permissible line length L as a function of consumption P and as a parameter of the cross-sectional area. 4626D02en L [m] 300 200 2.5 mm² 0.75 mm² 100 1 mm² 1.5 mm² 0.5 mm² 0 8 0 Notes on diagram · · P&I diagram: Voltage drop on the supply lines 16 24 The values in [VA, W] on the P-axis are allocated to the permissible voltage drops (DU/2U = 4 %) on line L as per the above table and to the P&I diagram.
The following sections show how to determine the permissible line length and crosssectional areas for the various actuators based on examples. The examples for actuators connected in parallel apply to the following arrangement: G0 G L2 A1 L2 A2 L2 A3 L2 A4 G0 G L1 G0 G Controller G0 L1 G G0 G G0 G Assumption 4614S01en Line length for actuators connected in parallel The line resistances of L2 are equal and can be ignored for L1.
Note: 2-position control It is recommended to switch off the power during two-position control when the actuator has reached the open or close position, in order to enhance life span and reduce power consumption. 6.3 Modulating actuators GBB/GIB16..1 Power consumption and perm. voltage drop with one actuator P&I diagram: Currents Actuator wiring (modulating) With AC supply, the G0 line has a AC 0.33 A supply current and a DC 0.1 mA positioning signal current (from Y = DC 0...10 V).
6.4 Actuator wiring (Modbus RTU) The damper actuators are supplied with a prewired connecting and communication cable. All interconnected devices must be connected to the same G0.
7 References Commissioning notes All information necessary for commissioning is contained in the following: · This document ("Technical basics" Z4626en) · Mounting instructions 4 319 2685 0 (M4626) · HVAC plant diagram 7.1 Environmental conditions Mechanical check Electrical check Check to ensure that all permissible values as contained in chapter 8 Technical data are observed. · Check for proper mounting and to ensure that all mechanical settings correspond to the plant-specific requirements.
Position indicator Check of output voltage U: · U = DC 0...10 V for angular rotation 90°. Feedback potentiometer Measures resistance changes while the actuator turns from 0 to 90°. Auxiliary switches A and B · · Switchover of the auxiliary switch contacts "A" and "B" as soon as the actuator reaches the respective switching positions. Set the setting shafts (part of the delivery) to the desired value by means of a screwdriver (see section 3.2 "Angular range and mechanical limitation”).
Push button operation 7.3 Modbus 7.3.1 HMI – Human-machine interface Activity Push-button operation Confirmation Display current address Press button < 1s 1-digits: red (starting with lowest address digit) 10-digits: green 100-digits: orange If termination is switched on, LED flashes 1x blue after address display Example: 124 = 4x red, 2x green, 1x orange Turn bus termination on / off turn on 1.press 3x LED flashing and flickering stops (termination mode) 2.
Resetting the device by push button 1. 2. 3. 4. Press button for >10s → LED starts flashing orange. Release button while LED still flashes → LED keeps flashing for 3s. If the button is pressed within these 3s, the reset is cancelled. After those 3s → LED shines red (reset), then the device restarts. 7.3.2 Push button addressing The Modbus address can be set without a separate tool by using push-button and LED. To display the current address, press button <1s.
Set address “5”: 1. Enter addressing mode 2. Set 1- digit: Press button 5-times → LED flashes green per button press Store address: press button until LED shines red → address is stored and displayed 1x for confirmation 7.3.3 Commissioning Workflow 1 The devices are especially designed for using the Climatix push-button configuration as described in document A3975 1). The bus configuration can alternatively be parameterized by the local HMI, cf. page 29.
7.3.4 Modbus registers Reg. Name R/W Unit Scaling Range / enumeration Process Values 1 Setpoint RW % 0.01 0..100 2 Override control RW -- -- 0 = Off / 1 = Open / 2 = Close 3 = Stop / 4 = GoToMin / 5 = GoToMax 3 Actual position R % 256 Command RW -- 0.01 0..
Reg. Name R/W Value Example Device information 1281 Factory Index R Two bytes, each 00 5A à 00 “Z” coding an ASCII char.
7.3.5 Parameter and function description Function Reg. Description Override control 2 The actuator can be operated in override control for commissioning / maintenance purposes or system-wide functions (e.g. night-cooling). · Manual override: When the gear disengagement is used to freely adjust the damper position, a mechanical jam will be detected if a mismatch between setpoint and actual position persists for more than 10s.
8 AC 24 V supply (SELV/PELV) AC 230 V power supply Functional data Technical data Operating voltage Frequency Safety extra-low voltage (SELV) or Protective extra-low voltage (PELV) as per Requirements for external safety isolating transformer (100 % duty) Supply line fuse Power consumption GBB/GIB13..1: Running GBB16.1/GIB16..1..: Running GBB/GIB16..1: Holding Operating voltage Frequency Supply line fuse Power consumption: GBB/GIB33..
Auxiliary switches for GBB/GIB136.1, GBB/GIB336.1 GBB/GIB164.1, GBB/GIB166.1 Connection cables Degree of protection of housing Protection class Environmental conditions Standards and directives Permissible voltage at potentiometer (SELV/PELV) Insulation resistance between potentiometer and housing Contact rating Life: 6 A res., 2 A ind. 5 A res., 1 A ind.
9 Diagrams 9.1 Internal diagrams GBB/GIB13..1 / GBB/GIB33..1 GBB/GIB16..1 Three-position control Modulating control S4 B 2 B A 9.2 4626G03 (Q24) S2 S3 (Q22) 9 S5 S6 4626G02 (Q24) S2 S3 (Q22) (Q12) (Q14) (N) 4 B DC 0..10 V M 0% (Q12) (G0) (Q11) 100% A S4 0% S4 (Q21) S1 (c) (b) (Y1) (Y2) P1 P2 P3 (a) 7 S1 M AC 24 V...230 V / 6 (2) A GBB/GIB33... 6 8 100% SELV/PELV 0...1000 W AC 24 V...230 V / 6 (2) A (Q21) 1 SELV/PELV DC 0..10 V (Y) GBB16... GIB16...
9.3 SP 4626A03 GBB/GIB13..1 AC 24 V Connection diagrams (three-position control) (G) Q1 Q2 AC 24 V (G0) (Y1) (Y2) 6 7 N P1 P2 P3 S1 S4 GBB/GIB13... Y 1 S2 S3 S5 S6 S1 S4 SN L Controller Actuator GBB/GIB13..1 System potential AC 24 V System neutral Controller contacts N Y L N Q1, Q2 Controller Actuator GBB/GIB33..1 System potential AC 230 V System neutral Controller contacts 4626A04 GBB/GIB33..
9.4 Connection diagrams (modulating) 9.4.1 Typical application The controller output is connected directly to the actuator input. GBB/GIB16..1 SP (G) AC 24 V (Y) 1 (G0) N S1 S4 S2 S3 S5 S6 8 GBB/GIB16... 9 4626A05 Y 2 P SN 9.4.2 N Y P SP SN Controller Actuator GBB/GIB16..
GIB161.1E/MO 9.5 Connection diagrams (networked) 9.5.1 Typical application The application controller is connected to the actuator by the bus cable. 40/44 Siemens Smart Infrastructure Rotary actuators without spring return GBB/GIB..
10 General notes Environmental compatibility and disposal These actuators were developed and manufactured by using environmentallycompatible materials and by complying with our environmental standards. For disposal, please remember the following at the end of product life or on defects: · As a rule, dispose of all waste in an environmentally compatible manner and in accordance with environmental, recycling, and disposal techniques. Ad-here to all local and applicable laws.
11 Chapter contents Appendix This chapter contains: · Actuator dimensions · Referenced documents 11.1 Dimensions Dimensions in mm A6V101006034M01 External Modbus Interface X = 220 mm Dimensions in mm 42/44 Siemens Smart Infrastructure Rotary actuators without spring return GBB/GIB..
11.2 Referenced documents Purpose of this listing The previous chapters contain all information relevant to safety and project-specific requirements, mounting, wiring, and commissioning of actuators. Documents and standards The following list contains all documents referenced by this document on basics: · · · Data sheets (N....) with detailed specifications Basic documentation (Z....) with basics on air damper actuators Mounting instructions (M….
Accessories for type series GBB/GIB..1 N4699en (N4699) N4615en (N4615) 74 319 0413 0 (M4615) 4 319 2659 0 (M4626.1) 4 319 2708 0 (M4626.2) 4 319 2725 0 (M4626.3) 4 319 2846 0 (M4626.4) 74 319 0236 0 (M4614.1) 4 319 2849 0 (M4613.1) 4 319 2950 0 Standards Accessories and spare parts for air dampers actuators ASK7.. External Auxiliary Switches ASC77.. External Auxiliary Switches ASC77.. Rotary/linear set for duct mounting ASK71.1 Rotary/linear set for frame mounting ASK71.