Basic Documentation

37/44
Siemens Rotary actuators without spring return GBB/GIB..1 CE1Z4626en
Smart Infrastructure Diagrams 2019-11-28
9 Diagrams
9.1 Internal diagrams
GBB/GIB13..1 / GBB/GIB33..1 GBB/GIB16..1
Three-position control
4626G01
A100%
0%
(Y2)
AC 0 V
0...1000 W
AC 24 V...230 V / 6 (2) A
(a)
(G)
(Q12)
(Q14)
(Q24)
(Q22)
1
S2 S3 S5 S6
7 P3 S1 S4
(Q11)
(Q21)
B
(Y1)
(b)
(c)
6 P1 P2
AC 24 V
M
SELV/PELV
GBB/GIB13...
4626G02
A100%
0%
(Y2)
AC 230 V
0...1000 W
AC 24 V...230 V / 6 (2) A
(a)
(N)
(Q12)
(Q14)
(Q24)
(Q22)
4
S2 S3 S5 S6
7 P3 S1 S4
(Q11)
(Q21)
B
(Y1)
(b)
(c)
6 P1 P2
M
SELV/PELV
GBB/GIB33...
Modulating control
DC 0...10 V / 0...35 V
A
100%
0%
DC 0..10 V
(G)
AC 24 V
DC 0..10 V
GIB16...
(Y)
(G0)
(U)
(Q12)
(Q14)
(Q24)
(Q22)
2 9
S2 S3 S5 S6
1 8 S1 S4
(Q11)
(Q21)
B
AC 24 V...230 V / 6 (2) A
GBB16...
SELV/PELV
M
9.2 Cable labeling
All wires are color-coded and labeled.
Pin
Cable
Meaning
Code No. Color
Abbreviation
Actuators G 1 red RD System potential AC 24 V
AC 24V G0 2 black BK System neutral
Y1 6 purple VT Pos. signal AC 0 V, "clockwise"
Y2 7 orange OG Pos. signal AC 0 V, "counter-clockwise"
Y 8 grey GY Pos. signal DC 0...10 V, 0...35 V
U 9 pink PK Position indication DC 0...10 V
Modbus types REF 6 violet VT Reference (Modbus RTU)
+ 8 gray GY Bus + (Modbus RTU)
- 9 pink PK Bus - (Modbus RTU)
Actuators N 4 blue BU Neutral
AC 230V Y1 6 black BK Pos. signal AC 230 V, "clockwise"
Y2 7 white WH Pos. signal AC 230 V, "counter-clockwise"
Auxiliary switches Q11 S1 grey/red GY RD Switch A input
Q12 S2 grey/blue GY BU Switch A normally-closed contact
Q14 S3 grey/pink GY PK Switch A normally-open contact
Q21 S4 black/red BK RD Switch B input
Q22 S5 black/blue BK BU Switch B normally-closed contact
Q24 S6 black/pink BK PK Switch B normally-open contact
Feedback a P1 white/red WH RD Potentiometer 0...100 % (P1-P2)
potentiometer b P2 white/blue WH BU Potentiometer pick-off
c P3 white/pink WH PK Potentiometer 100...0 % (P3-P2)