User Manual
4/6
Siemens Air damper actuators for laboratory applications GAP19… CE1N4608en
Smart Infrastructure 2019-09-27
Technical data
Operating voltage / Frequency
Power consumption: Actuator running
Hold
AC/DC 24 V ± 20 % / 50/60 Hz
30 VA / 22 W
5 W
Nominal torque
Maximum torque (when blocked)
Nominal rotary angle / max. rotary angle
Runtime for 90° rotary angle
6 Nm
18 Nm
90° / max. 95° ± 2°
2 s
Input voltage Y/Y1+ (wires 8-2)
Positioning resolution for DC 0 (2)...10 V / 0 (4)…20 mA
Max. permissible input voltage
DC 0 (2)...10 V / 0 (4)…20 mA or
AC/DC 0 V , AC/DC 24 V "open"
250 steps for 90 °
AC/DC 24 V ± 20 %
Input voltage Y2+ (wires 7-2)
Max. permissible input voltage
AC/DC 0 V , AC/DC 24 V "close“
AC/DC 24 V ± 20 %
Output voltage U (wires 9-2)
max. output current
DC 0 (2)...10 V
DC ± 1 mA
Contact loading
Voltage (no mixed operation AC 24 V / AC 230 V)
Switching range for auxiliary switches
Setting increments
6 A resistive, 2 A inductive
AC 24...230 V
5°...90°
5°
Cross-sectional area
Standard length
0.75 mm
2
0.9 m
Protection class as per EN 60 529 (observe mounting notes) IP 54
Insulation class
230 VAC, auxiliary switch
EN 60 730
ll
Operation / Transport
Temperature
Humidity (non-condensing)
IEC 721-3-3 / IEC 721-3-2
-32...+50 °C / -32...+70 °C
< 95% r. h. / < 95% r. h.
Product safety: Automatic electronic controls for household and
similar use
EN 60 730-2-14
(Type 1)
Electromagnetic compatibility (Application) For residential, commercial and
industrial environments
EU Conformity (CE) A5W00004380
1)
RCM Conformity A5W00004381
1)
Product environmental declaration
2)
CE1E4608en
1)
Actuator W x H x D (see Dimensions)
Damper shaft: round
square
Min. shaft length
81 x 192 x 63 mm
6.4… 20.5 mm
6.4… 13 mm
20 mm
Excl. packaging 1.260 kg
1)
 The documents can be downloaded from http://siemens.com/bt/download
2)
 The product environmental declarations contains data on environmentally compatible product design
and assessments (RoHS compliance, materials composition, packaging, environmental benefit,
disposal).
Disposal
The device is considered an electronics device for disposal in terms of
European Directive 2012/19/EU and may not be disposed of as domestic
garbage.
● Dispose of the device through channels provided for this purpose.
● Comply with all local and currently applicable laws and
regulations.
 24 VAC/VDC supply
 (SELV/PELV)
Functional data
Positioning signal Y/Y1
Positioning signal Y2
Position indicator
 Auxiliary switch for GAP196
Connection cable
Housing type
Protection class
Environmental conditions
Norms and Directives
Dimensions
Weight