Siemens Air damper actuators for laboratory applications GAP19… CE1N4608en
Smart Infrastructure 2019-09-27
Type summary
Types Power
Auxiliary
switch
Torque Damper size Runtime
GAP191.1E
AC/DC 24 V
No
6 Nm Ca. 1 m
2
2 s
GAP196.1E Yes
When installing and operating rotary actuators type GxP191.1E and GxP196.1E in low-
noise environments, check the acoustic response of the actuators operated together
with the measuring and control equipment.
The combination with differential pressure sensors, sensors, and controllers may result
in unwanted operational noise based on the operating settings, regardless of the given
manufacturer.
·  Low-noise HVAC plants in general
1)
·  Supply and extract air plants
·  Fume hood control plants
·  Room pressure control plants
1)
e.g. Laboratories / fume hoods, hospital rooms or similar plants
We recommend using rotary actuator HLV40.1 if the applications listed above are
motorized or in the event of any general concerns regarding operational noise of GAP
actuators (Contact your local Siemens representative).
The actuator is preset at
the factory to:
· 0…10 V
· Clockwise rotary movement.
Note
Impacted applications
Alternative
Factory setting