Data Sheet for Product
2
Siemens
CE1N4608en
Smart Infrastructure 2021-11-
30
Use
● For damper areas up to ca. 1 m
2
, friction dependent
● For laboratory fume hoods, etc.
● Suitable for use with continuous, 2-position, or 3-position controllers
Functions
DIL switch setting A DIL switch is used to set the actuator's functionality.
Modulating control 2-position control 3-position control
Factory
setting
DC 0…10 V DC 2…10 V 0…20 mA 4…20 mA 2-Pt 3-Pt
Position indication
Mechanical Rotary angle position
Electrical Output voltage U = DC 0...10 V is generated proportional to rotary angle.
U depends on the DIL switch's rotary direction position.
Rotary angle limitation The rotary angle of the shaft adapter can be limited mechanically to 5° increments.
GAP196.1E auxiliary
switch
The switching points for auxiliary switches A and B can be set mutually independent in 5° increments from
0...90°.
Type summary
Type Power Auxiliary switch Torque Holding torque Damper size Runtime
GAP191.1E
AC/DC 24 V
No
6 Nm Reduced Ca. 1 m
2
2 s
GAP196.1E Yes