Output devices
Overview and selection guides
Binary output devices
Diagnostic functions
The diagnostic functions support supervisory systems with their
display, monitoring and archiving functions. For this purpose these
diagnostic functions are available:
Device function: The switching actuator cyclically sends a function
signal allowing a supervisory system to control its function.
Status indication: Sending of the switching status can be activated
per output. The current status can be read via the bus or transmitted
cyclically.
Status retrieval: For all outputs sending the current status can be
triggered via a central status retrieval object. With a single message a
visualization (e.g. IP Control Center) can update its status informa-
tion and display.
Switching cycle count with or without threshold monitoring: The
switching cycle count can be activated per output. The number of
switching cycles can be read via the bus. This allows for monitoring
of the switching cycles and a switching cycle dependent mainte-
nance. If the threshold monitoring is activated the device sends a
signal onto the bus when the set threshold is reached. The excee-
dance of the threshold is automatically signaled respectively this can
be sent as an email by the IP Control Center or can be displayed by a
warning light.
Operating hour count with or without threshold monitoring: The
operating hour count can be activated per output. The number of
operatin
g hours can be read via the bus. This allows for monitoring
of the operating hours and an operating hour dependent
maintenance,
e.g. if after 10,000 hours of operation lamps shall be replaced. If the
threshold monitoring is activated the device sends a signal onto the
bus when the set threshold is reached. The exceedance of the
threshold is automatically signaled respectively this can be sent as an
email by the IP Control Center or can be displayed by a warning light.
The control, override and diagnostic functions can be realized in the
device itself without additional control modules or a controller.
With these functions the switching actuators are getting into the
functional class of a micro-PLC with powerful relays.