Application Examples
KNX visualization via Ethernet (LAN)
Visualization – up to 200 times faster with KNXnet/IP
When retrieving large numbers of data points cyclically for visualization
in large projects, waiting periods can sometimes occur while data is
being updated.
Use your LAN as the main and backbone line and connect your PC
for visualization to the LAN. This makes visualization up to 200 times
faster: you can monitor larger numbers of data points and the data
volume is no longer important.
Benefits
LAN as the main and backbone line
Visualization up to 200 times faster than previously
High data volume possible
No data concentrators needed
Follow these steps
Commission the KNX devices, including the IP router N 146/02
Install the visualization software
Find and connect the IP router N 146/02 as the visualization interface
Configure the visualization
Observe the related safety and security requirements governing the
LAN
You will need
One IP router N 146/02 per line
IP Control Center N 152
24-V power supply for IP interface N 146/02, e.g. Power over
Ethernet, unchoked bus voltage
Ethernet network (LAN)
ETS; see knx.org for the latest version
Note:
LAN stands for Local Area Network. In LANs, data transport is orga-
nized using the IP (Internet Protocol) – the standard network protocol
on the Internet.
Multicast-capable: multicast telegrams can simultaneously operate
several IP devices in the LAN. In the case of network components (net-
work switches, routers) this requires the appropriate configuration.
The solution
KNX device
KNX device
KNX device
LAN-enabled PC with visualization
IP router
IP router
LAN
(multicast-enabled)
I201_15415
KNX KNX