System overview
System data
Bus cable
Cable type mm
2
YCYM 2 x 2 x 0.8
One core pair (red, black) for signal transmission and power supply, one
core pair (yellow, white) for additional applications (SELV or voice)
Cable length
Cable lengths of one line in total (core diameter: 0.8 mm) m max. 1000 (including all junctions)
Length between two bus devices m Max. 700
Length between bus device and power supply unit (320 mA)/choke m Max. 350
Length between power supply unit (320 mA) and choke
Side-by-side mounting necessary
(on standard mounting rail with integrated data rail)
Bus devices
Number of areas Max. 15
Number of lines per area Max. 15
• Number of bus devices per line Max. 64
Topology
• Topology structure Line, star or tree structure
Power supply
Power supply V DC 24 (SELV safety extra-low voltage)
• Power supply units per line Minimum one power supply unit (160, 320 or 640 mA or 2 x 640 mA)
Transmission
Transmission technology Distributed, event-controlled, serial, symmetric
Baud rate bit/s 9600
Device characteristics (unless otherwise specified)
Device properties
Degree of protection according to EN 60529 IP20
Protective measure Bus: safety extra-low voltage SELV 24 V DC
Overvoltage category III
Rated insulation voltage Ui V 250
Degree of pollution 2
EMC requirements complies with EN 50428
Resistance to climate EN50491-2
Operating conditions
Application
For fixed installation indoors, for dry rooms and installation in heavy-
current distribution boards
Ambient operating temperature °C -5 to +45
Humidity in operation % Max. 93
Storage temperature °C -25 to +70
Humidity in storage % Max. 93
Certification KNX/EIB certified
CE marking
Compliant with EMC Directive (residential and non-residential buil-
dings), Low Voltage Directive
1515
39_VS_2017_Gamma HQ_EN_Chapter_15_V1.indd 5 26.07.2018 15:24:47