User Manual

13-6
Siemens Switzerland Ltd www.siemens.com/gamma 2019
Building Technologies Division
System products and accessories
Technical specication
Bus coupling units and accessories, Power supply units
Bus coupling units and accessories
Type UP 117/12
UP 116/01
UP 116/21
UP 116/11
UP 116/31
Enclosure data
For installation in flush-mounting switch and
socket boxes with Ø = 60 mm
n n n
For mounting rockers from the DELTA product
ranges
n n
10-pole BTI socket connector
(BTI: Bus-Transceiver-Interface) for
plugging onto a bus terminal
n
Dimensions
Width [mm] 71 71 71
Height [mm] 71 71 71
• Depth [mm] 18 32 32
Mounting type
Claw fixing n n
Screw fixing n n n
Display/control elements
LED for status indication n n
LED for orientation light n n
Bus connection
Integrated bus coupling units n n n
Bus connection via bus terminal n n n
Power supply units
Type N 125/02 N 125/12 N 125/22 RL 125/23 JB 125C23
Enclosure data
Modular installation devices for mounting on
TH35 EN 60715 mounting rail
n n n
Device for installation in Control Module Box
AP 118 or Room Control Box AP 641
n
Device for installation in Junction Box 4” x 4 n
Dimensions
• Width (1 MW = 18 mm) 4 MW 4 MW 4 MW 47,8 mm 70 mm
• Height [mm] 86,5 mm 90 mm
• Depth [mm] 36,2 mm 44,6 mm
Bus connection
Integrated chokes n n n n n
Bus connection optional via contact system to
data rail
n n n
Bus connection via bus terminal n n n n n
Outputs
Rated operational voltage
V AC 120...230 120...230 120...230 120...230 120...230
• V DC 220 220 220 220 220
50...60 Hz n n n n n
Output voltage, DC [V] 29 29 29 29 29
Output current [mA] 160 320 640 80 80
Additional unchoked output for 29 V DC, for
powering a second bus line via an external choke
(e. g. N 120/02)
n n n
Number of decentralized power supplies installed
in parallel on the same bus line
8 8 7 8 8
13 13
30_VS_2017_Gamma HQ_EN_Chapter_13_V1.indd 6 26.07.2018 15:18:59