User Manual
11-23
Physical sensors
without KNX connection
Humidity
Siemens Switzerland Ltd
Building Technologies Division
2019www.siemens.com/gamma
11
Stock No. Product No. DT
BPZ:QFA2060 QFA2060 A
Connectable with temperature sensor N 258/02 (5WG1258-1AB02), see chapter Physical Sensors - with KNX connection.
QFA2060Room sensor for humidity (DC 0...10 V) and temperature (DC 0...10 V)
• For relative humidity and temperature.
Data sheet N1857
Signal output humidity DC 0...10 V
Signal output temperature DC 0...10 V
Operating voltage AC 24 V
DC 13.5...35 V
Measuring range, temperature 0...50 °C
-35...35 °C
-40...70 °C
Stock No. Product No. DT
BPZ:QFA2060D QFA2060D C
Connectable with temperature sensor N 258/02 (5WG1258-1AB02), see chapter Physical Sensors - with KNX connection.
QFA2060DRoom sensor for humidity (DC 0...10 V) and temperature (DC 0...10 V), with
digital Display
• For relative humidity and temperature.
Data sheet N1857
Signal output humidity DC 0...10 V
Signal output temperature DC 0...10 V
Operating voltage AC 24 V
DC 13.5...35 V
Measuring range, temperature 0...50 °C
-35...35 °C
-40...70 °C
Stock No. Product No. DT
BPZ:QFA1000 QFA1000 A
QFA1000Room hygrostat, setpoint setting range 30...90 % r.h., setpoint adjuster inside
device
• 2-position controller with humidity sensor
• Setpoint adjuster inside device
Data sheet N1518
Setpoint setting range 30...90 % r.h.
Switching differential 6 % r.h.
Time constant At v = 0.2 m/s: 5 min
Digital outputs 1-pin
Potential-free
Changeover contact
Connection, electrical Screw terminals
Digital output, switching voltage AC 230 V
Digital output, switching current 5 (3) A
Degree of protection IP20
Dimensions (W x H x D) 76 x 76 x 34 mm
21-Temperature.indd 23 26.07.2018 15:10:34