User Manual

11-15
Physical sensors
with KNX connection
Temperature, humidity, air quality
Siemens Switzerland Ltd
Building Technologies Division
2019www.siemens.com/gamma
11
Range overview AQR253..
Measuring range,
temperature
[°C]
Signal output
temperature
Measurement
range
humidity
[%]
Display Stock No. Product No. DT
S55720-S137 AQR2530NNW A
0…50 Active S55720-S136 AQR2532NNW A
0…50 Active 0…100 S55720-S141 AQR2535NNW A
0…50 Active 0…100 CO2 indicator by LED S55720-S219 AQR2535NNWQ A
Matching the DELTA line and DELTA miro frame program. See chapter Display and Operation Units.
The relevant base modules must be ordered separately. See chapter Physical sensors - Without KNX connection.
Front modules for base modules
Front module with sensors
Matching the DELTA line and DELTA miro frame program
Data sheet N1411
Color Titanium white
Degree of protection IP30
Dimensions (W x H) 55 x 55 mm
AQR253..
Range overview AQR2576..
Mechanical design Dimensions (W x H) Stock No. Product No. DT
EU (CEE/VDE) 70.8 x 70.8 mm S55720-S207 AQR2576NF A
IT (3 Modular) 110 x 64 mm S55720-S209 AQR2576NG C
UK (British Standard) 83 x 83 mm S55720-S208 AQR2576NH C
US (UL) 64 x 110 mm S55720-S210 AQR2576NJ A
Base modules with KNX for CO
2
measurement
Base module with maintenance and recalibration-free CO2 sensor to plug onto a front module
1 analog input to connect temperature sensors with NTC 10k sensing element to measure room, oor,
or ceiling temperature
2 multifunctional binary inputs to connect window contacts or buttons
Power supply via KNX bus, bus load < 5 mA
Ventilation control across 3 settable switching steps for relative humidity & CO2 concentration, and 3
switching signal objects On/Off, or one positioning signal object 0…100% to control a ventilation actor
Temperature control as continuous control (PID algorithm) for pure heating operation, heating and
cooling operation, and adjustable positioning variable as continuous positioning signal 0…100%, or as
pulse-width modulated (PWM) switching signal On/Off
Via setpoints for room temperature and relative humidity, and CO2 concentration, adjustable via KNX
bus
Adjustable commissioning and control parameters
Integrated bus coupler with programming button and LED
Data sheet N1411
Voltage supply KNX bus
Measuring range CO
2
: 0...5000 ppm
Analog inputs, number 1
Analog inputs Passive temperature sensor NTC 10k
Digital inputs, number 2
Digital inputs Potential-free contacts
AQR2576..
5-Motion_presence.indd 15 26.07.2018 15:11:23