User Manual

11-11
Physical sensors
with KNX connection
Temperature, humidity
Siemens Switzerland Ltd
Building Technologies Division
2019www.siemens.com/gamma
11
Stock No. Product No. DT
S55720-S141 AQR2535NNW A
Matching the DELTA line and DELTA miro frame program. See chapter Display and Operation Units.
The relevant base modules must be ordered separately. See chapter Physical sensors - Without KNX connection.
AQR2535NNWFront module for base module, humidity and temperature (active)
Front module with humidity and temperature sensor for plugging onto the Base module
Matching the DELTA line and DELTA miro frame program
Data sheet N1411
Measuring range, temperature 0…50 °C
Signal output temperature Active
Measurement range humidity 0…100 %
Range overview AQR2570..
Mechanical design Dimensions (W x H) Stock No. Product No. DT
EU (CEE/VDE) 70.8 x 70.8 mm S55720-S203 AQR2570NF A
IT (3 Modular) 110 x 64 mm S55720-S205 AQR2570NG A
UK (British Standard) 83 x 83 mm S55720-S204 AQR2570NH C
US (UL) 64 x 110 mm S55720-S206 AQR2570NJ A
Base module with KNX for temperature and humidity measurement
Base module without sensor for plugging onto a front module
1 analog input to connect temperature sensors with NTC 10k sensing element to measure room, oor,
or ceiling temperature
2 multifunctional binary inputs to connect window contacts or buttons
Power supply via KNX bus, bus load < 5 mA
Temperature control as continuous control (PID algorithm) for pure heating operation, heating and
cooling operation, and adjustable positioning variable as continuous positioning signal 0…100%, or as
pulse-width modulated (PWM) switching signal On/Off,
Ventilation control across 3 settable switching steps for relative humidity, and 3 switching signal
objects On/Off, or one positioning signal object 0…100% to control a ventilation actor
Via setpoints for room temperature and relative humidity adjustable via KNX bus
Adjustable commissioning and control parameters
Integrated bus coupler with programming button and LED
Data sheet N1411
Voltage supply KNX bus
Analog inputs, number 1
Analog inputs Passive temperature sensor NTC 10k
Digital inputs, number 2
Digital inputs Potential-free contacts
AQR2570..
5-Motion_presence.indd 11 26.07.2018 15:11:21