User Manual

11-3
Siemens Switzerland Ltd www.siemens.com/gamma 2019
Building Technologies Division
Physical sensors
Technical specication
Physical sensors with KNX connection
Physical Sensors with KNX connection
Type
UP 258E22
UP 258D12
AP 251/..1
UP 258D21
N 258/02
AP 254/02
AQR257..
QMX3..
Enclosure data
Mounting
1)
UP/AP AP UP N AP UP AP
Degree of protection IP20 IP55 IP20 IP20 IP54 IP20 IP30
Dimensions
• Width/Ø [mm] (1 MW = 18 mm) 88 82 88 4 MW 72 71 89
• Height [mm] 63
2)
80 63
2)
110 71 134
• Depth [mm] 182 54 39 18
Power supply
Bus-powered electronics KNX KNX KNX AC 230V KNX KNX KNX
Bus connection
Integrated bus coupling units n n n n n n n
Plug onto UP 110 bus coupling unit
Bus connection via bus terminal n n n n n n n
Bus connection via contact system to
data rail
n
Transmission of sensor values via bus n n n n n n n
Motion/presence
Motion n n
Presence n
HVCA message output n
Horizontal sensing angle 360° 290°
Vertical sensing angle 105°
Range to the front [m] 8
Range on each side, up to [m] 7
3)
16
Adjustable range
Brightness
Measuring range [Lux] 20...1000 20...1000 1...100000
For measuring outdoor brightness n
For measuring indoor brightness
(mixed light)
n n
Temperature
Measuring range [°C] -40...+150 -25...+55 0...50
4)
0...50
4)
Temperature sensor inputs 4 x Pt1000 NTC 10k
4)
Max. cable length, unshielded, twisted
[m]
50 10
7)
Humidity [% r.F.] 0...100
4)
0...100
4)
CO2 [ppm] 0...5000
4)
0...5000
4)
1)
AP surface mounted, UP flush mounted
2)
For flush mounting, mounting height approx. 31 mm, for surface mounting with AP 258E surface-mounting enclosure, approx. 73 mm. In conjunction
with AP 258E surface-mounting enclosure
3)
For complete technical data visit www.siemens.de/gamma-td
4)
Only with according combination or variant available
1111