User Manual

10-5
Siemens Switzerland Ltd www.siemens.com/gamma 2019
Building Technologies Division
Gateways, interface converters
Technical specication
KNX/DALI
KNX/DALI
Type N 141/21 N 141/03 N 141/31 N 525E
Name Twin plus plus Twin
Enclosure data
Design N N N N
Modular installation devices for mounting on TH35 EN 60715
mounting rail
n n n n
Dimensions
Width [mm] (1 MW = 18 mm) 4MW 4 MW 4 MW 4 MW
Display/control elements
Status indication per output LED + 7 Segment LED + 7 Segment LED + 7 Segment LED
Power supply
Electronics powered via an integrated power supply unit n n n n
DALI outputs powered via an integrated power supply unit n n n n
Power loss
Max. power loss [W] 11 6 11 6
Bus connection
Integrated bus coupling units n n n n
Bus connection via contact system to data rail n
Bus connection via bus terminal n n n n
Outputs
Control outputs
DALI outputs (lines) 2 1 2 8
DALI output acc. to IEC 60929 for DALI ECG
(16 V, floating, short-circuit resistant)
n n n n
Max. ECG per output 64 64 64 8
Selected DALI sensors n n n
Functions
Direct operation n n n n
Broadcast operation n n n n
Standalone operation n n n
Configurable behavior in the event of a bus voltage failure/
recovery
n n n n
Support of CIN n n
Scene control
Integrated 8-bit scene control n n n n
Scenes to be integrated per DALI output 16 16 16 16
Effect control
Integrated effect control (one-off or cyclic chaselight operation,
color control)
4 4
Test function via ETS
Testing individual ECGs n n n
Testing group assignment n n n
Testing scenes n n n
Testing effects n n
Group control
Up to 16 groups per DALI output
• Switching ON/OFF n n n
BRIGHTER/DARKER dimming n n n
• Set value n n n
Individual ECG control
Operation of individual ECG with
Switching ON/OFF n n n
1)
BRIGHTER/DARKER dimming n n n
1)
• Set value n n n
1)
ETSApp in KNX Online Shop n n n
Pre-loaded applications n n
Replace defective ECG without software n n n n
1)
Only with application program 983Dxx
1010
24_VS_2017_Gamma HQ_EN_Chapter_10_V1.indd 5 26.07.2018 14:38:18