User Manual

Heating, ventilation and air conditioning - primary control
Communicating controllers - Synco™ 700
Universal controllers RMU7..0B..
8-8
Siemens Switzerland Ltd
Building Technologies Division
2019www.siemens.com/gamma
8
Range overview RMU7..0B..
Analog outputs,
number
Universal inputs,
number
Relay outputs,
number
Control loops,
number
Stock No. Product No. DT
2 6 2 1 BPZ:RMU710B-1 RMU710B-1 A
3 8 4 2 BPZ:RMU720B-1 RMU720B-1 A
4 8 6 3 BPZ:RMU730B-1 RMU730B-1 A
Universal controller
Universal controllers with integrated control and supervisory functions
Suited for the controlled variables temperature, relative / absolute humidity, pressure / differential, air
ow rate, indoor air quality, etc.
Autonomous sequence controllers with P, PI or PID mode
Tested, predened applications (refer to Application Catalog)
Flexible conguration
Clear-text operation with separate operator unit (plug-in type or detached)
Integrated KNX bus communication
No commissioning tool required
The RMU7..0B-1 supports the languages: English, German, French, Italian, Spanish, Portuguese, Dutch,
Danish, Finnish, Norwegian, Swedish, Polish, Czech, Hungarian, Russian, Slovak, Bulgarian, Greek, Roma-
nian, Slovenian, Serbian, Croatian, Turkish, Chinese.
Extension modules complement the universal controller and offer extra functions. They are attached to
the controller via plug-in connectors. The extension modules do not operate autonomously.
The operation of the device from commissioning to enduser operation can be done via the operator unit.
Available extension modules:
1 universal module RMZ785
2 universal modules RMZ787
2 universal modules RMZ788
A total of 4 extension modules can simultaneously be used with the universal controller.
Available operator units:
Plug-in type operator unit RMZ790
Detached operator unit RMZ791
Bus operating unit RMZ792
Data sheet N3150
Operating voltage AC 24 V
Frequency 50/60 Hz
Power consumption 12 VA
Communication KNX (KNX TP1)
Analog output, signal DC 0...10 V
Analog output, current Max. 1 mA
Universal input, signal LG-Ni1000
2 x LG-Ni1000
T1 (PTC)
Pt1000
0...1000 Ohm
1000...1175 Ohm
DC 0...10 V
Digital pulse contact
Potential-free digital status contact
Relay output, switching voltage AC 19...250 V
Relay output, switching current 4 (3) A
Degree of protection IP20
Dimensions (W x H x D) 173 x 90 x 80 mm
RMU7..0B-1