Stock No. Product No. DT
BPZ:RXZ20.1 RXZ20.1 A
RXZ20.1Terminal cover for RXB2../ RXC2../ RXM2..
Data sheet N3834
Stock No. Product No. DT
BPZ:RXZ30.1 RXZ30.1 A
RXZ30.1Terminal cover for RXB3../ RXC3../ RXM3..
Data sheet N3840
Room unit with PPS2 interface
Room units for acquiring the room temperature and operation of individual room control.
Voltage supply PPS2
Power consumption 0.10 VA
Time constant ≤8 min
Measuring range, temperature 0...40 °C
Sensing element, temperature NTC
Measurement accuracy ±0.25 K at 25 °C
±0.5 K at 5...30 °C
Setpoint readjustment range ±12 K
Mounting location Indoors
Mounting Directly on wall
In recessed or top-mounted conduit box
Degree of protection IP30
QAX3..
Stock No. Product No. DT
BPZ:QAX30.1 QAX30.1 A
QAX30.1Room unit with sensor and PPS2 interface
- Acquisition of room temperature
Data sheet N1741
Dimensions (W x H x D) 90 x 100 x 32 mm