Heating, ventilation and air-conditioning – room temperature control
Technical specications
Electrothermal valve actuators without KNX
Electrothermal valve actuators without KNX
Type STA23 STA63 STA73 STP23 STP63 STP73 SSA31 SSA61 SSA81
Enclosure data
Dimensions
• Width/Ø [mm] 44 44 44 44 44 44 48 48 48
• Max. height [mm] 74 74 74 74 74 74 77 77 77
• Min. height [mm] 69 69 69 69 9 69 77 77 77
Output
• 230 V AC n n n
• 24 V AC n n n n n n
• 24 V DC n n n
Control signal Two-step 0 ... 10 V DC Two-step Two-step 0 ... 10 V DC Two-step Three-step 0 ... 10 V Three-step
Valve position in de-energized state
1)
NC NC NC NO NO NO NC NC NC
Fail Safe Function Y Y Y Y Y Y N N N
Max. lift [mm] 4.5 4.5 4.5 4.5 4.5 4.5 5.5 5.5 5.5
Max. positioning force [mm/N] 100 100 100 100 100 100 100 100 100
Max. open/close time [sec.] 210 270 270 210 270 270 330 75 330
Length of connecting lead [m] 1 2 1 1 2 1 1.5 1.5 1.5
Ambient temperature for operation [°C] +5 ... +50 +5 ... +50 +5 ... +50 +5 ... +50 +5 ... +50 +5 ... +50 +1 ... +50 +1 ... +50 +1 ... +50
Power Consumption [W/VA] 2.5 W 2.5 W 2.5 W 2.5 W 2.5 W 2.5 W 6 VA 2.5 VA 0.8 VA
Mounting 360°, also upside down 180°, not upside down
Degree of protection IP54 IP54 IP54 IP54 IP54 IP54 IP40 IP40 IP40
1)
Closed (NC), open (NO).
For further information regarding accessories (adapter, connector cable, ...) use the HIT-portal: www.siemens.com/hit