Solar protection, anti-glare protection, utilization of daylight
Technical specications
Load data for shutter/blind actuators per channel
Load data for shutter/blind actuators per channel
Type
N 501
N 523/02
N 523/03
N 523/04
N 523/11
N 522/03
N 524
RL 521/23
JB 521C23
UP 520/03
UP520/13
RS 520/23
JB 520C23
Contact current
Rated current [A] 6 (AC) 6 (AC) 6 (AC) 8 (AC) 1 (DC) 6 (AC) 6 (AC) 6 (AC) 6 (AC)
AC3 operation (p.f. = 0.45)[VA] 200 200 200 200 200 500 500 500 500
Contact voltage
Rated voltage [V] AC 230 AC 230 AC 230 AC 230 DC 24 AC 230 AC 120 AC 230 AC 120
Service life
Mechanical service life
Switching operations in millions
20 20 20 20 20 10 10 10 10
Electrical service life
Switching operations in millions
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
Power loss
Maximum power loss per device at
rated power [W]
7 3 5 8 6 5 5 3 3
Switching capacities/load types, loads
Resistive load [W] 1380 1380 1380 1840 24 1380 1380 1380 1380
Minimum switching capacity [V/mA] 6/10 6/10 6/10 7/10 8/10 24/10 24/10 24/10 24/10
DC switching capacity [V/A] 24/6 24/6 24/6 24/8 24/1 30/10 30/10 30/10 30/10
For complete technical specifications, see: www.siemens.com/gamma-td