Lighting
Technical specications
Light level controls
Constant light control for up to five light groups
Daylight
ABCDE
Artificially
light
500 Lux
Integrated constant light level controller with main lighting group
and up to four lighting subgroups with one brightness sensor
Automatic assignment of the artificial light distribution in the room
to enable constant light level control of the up to five lighting groups
via control charcteristics
Entry of five brightness values, measured under the lights during
pure daylight, as a parameter in ETS
Automatic measurement of artificial lighting in the room when it
is dark (without daylight) through targeted on/off switching of the
lighting groups and simultaneous measurement at the brightness
sensor of the detector
Function overview
A
B
C
D
M
The maximum detection ranges to be achieved are as follows divided:
A
Sitting person: moving hand ~ 25 cm at working desk height 0.8 m
B
Walking person s
traight: Step ~ 1 m straight to detector at floor level
C
Walking person: Step ~ 1 m across the detector at floor level
D
Brightness area at working desk height 0.8 m
M
Mounting height from floor level
Maximum achievable detection ranges
for UP 258E22 / UP 258D12 (in meters)
M A B C D
5,0 Ø 8,5 Ø 14 Ø 3,0
4,0 Ø 7,5 Ø 12 Ø 2,3
3,5 Ø 5,5 Ø 6,5 Ø 10 Ø 2,0
3,0 Ø 5,0 Ø 6,0 Ø 8 Ø 1,6
2,5 Ø 4,5 Ø 5,0 Ø 7 Ø 1,2