User Manual

5-14
Siemens Switzerland Ltd www.siemens.com/gamma 2019
Building Technologies Division
Lighting
Technical specications
Light level controls
Light level controls
Type UP 258E22 UP 258D12 UP 255D21 AP 254/02
Enclosure data
Design UP/AP UP/AP UP/AP AP
Dimensions
• Width/Ø [mm](1 MW = 18 mm) 88 88 88 72
• Height [mm] 63
1)
63
1)
63
1)
110
• Depth [mm] 54
Power supply
Bus-powered electronics n n n n
Bus connection
Integrated bus coupling units n n n n
Bus connection via bus terminal n n n n
Control
Integrated constant light level control 1-channel 1-channel
Integrated two-step control 1-channel 1-channel 1-channel
Light level controls dependent on surrounding light n
Offset groups 4 channels 4 channels
Sensors
Outdoor brightness n
Brightness (Contrast measurement) n n n
Motion ²
)
n n
Presence ²
)
n n
IR receiver
3)
n n n
¹
)
For flush mounting, mounting height approx. 31 mm, for surface mounting with AP 258E01 surface-mounting enclosure, approx. 73 mm.
²
)
Detection range see chapter Physical Sensors
3)
Use with IR remote control S 255/11
Constant light control for up to five light groups
Daylight
ABCDE
Artificially
light
500 Lux
Integrated constant light level controller with main lighting group
and up to four lighting subgroups with one brightness sensor
Automatic assignment of the artificial light distribution in the room
to enable constant light level control of the up to five lighting
groups via control charcteristics
Entry of five brightness values, measured under the lights during
pure daylight, as a parameter in ETS
Automatic measurement of artificial lighting in the room when it
is dark (without daylight) through targeted on/off switching of the
lighting groups and simultaneous measurement at the brightness
sensor of the detector
Function overview
Independent output channels Integrated light controller IR receiver
Type
Motion
Channel 1
(Lighting)
Presence
Channel 2
(Sun protec-
tion)
HVAC
Channel 3
(HVAC)
Locking
function
2-step light
control
(switching)
one lighting
group
Constant light
level control
(dimming)
up to five lighting
groups A - E
UP 258E22 Brightness sensor
Motion sensor
n n n n n n n
UP 258D12 Brightness sensor
Motion sensor
n n n n n n
UP 255D21
Brightness sensor
n n n
Device variants have identical functional units
Shared motion and brightness sensor for the output channels move-
ment and presence
Brightness-independent output channel for HVAC systems with special
evaluation logic
A switching 2-step light control and dimming constant light controller
independently usable
IR receiver for convenient operation of room functions
55