User Manual
5-12
Siemens Switzerland Ltd www.siemens.com/gamma 2019
Building Technologies Division
Lighting
Technical specications
Switching/dimming actuators
Switching/dimming actuators
Type N 526E02 N 526/02
Contact current
Rated current, AC [A] 16 6
Maximum switch-on peak current
• t = 150 s [A]
• t = 250 s [A]
• t = 600 s [A]
400
320
200
200
160
100
Contact voltage
Rated voltage, AC [V] 230 230
Service life
Mechanical service life Switching operations in millions 1 10
Electrical service life Switching operations in millions
1)
0.4
Power loss
Maximum power loss per device at rated power [W] 9 6
Switching capacities/load types, loads
Resistive load [W] 3680 1380
Minimum switching capacity [V/mA] 12/100
1)
DC switching capacity [V/A] 24/10 30/6
Maximum capacitive load [F] 140 163
Incandescent lamps
Incandescent lamps [W] 25 x 100 1380
Halogen lamp 230 V [W] 25 x 100 1380
LV halogen lamp with conventional transformer (inductive) [VA] 500 500
T5/T8 fluorescent lamps
Uncorrected [VA] 2500 1380
Parallel corrected (at max. possible C)[W] 1300 (140F) 1380 (163F)
DUO circuit [VA] 2500 1380
Compact lamps
Uncorrected [VA] 1600 1380
Parallel corrected (at max. possible C)[W] 1100 (140F) 1380 (163F)
1)
On request
The figures relate per channel. Complete technical data see: www.siemens.com/gamma-td
55