Type
N 501/01
N 502/02
N 605/01
UP 511/10
UP 562/31
UP 520/31
UP 525/31
UP 220/21
UP 220D31
Application program
1)
981701
981601
906101
207201
207101
207301
301901
982301
982201
Enclosure data
Design N N N UP UP UP UP UP UP
Modular installation device for mounting on
TH35 EN 60715 mounting rail.
n n n
For installation in flush-mounting switch and socket boxes with Ø = 60 mm n n n n n n
Dimensions
• Width/Ø [mm] (1 MW = 18 mm) 8 MW 8 MW 6 MW Ø 53 Ø 53 Ø 53 Ø 53 Ø 42 Ø 42
• Depth [mm] 28 28 28 28 8.5 8.5
Display/control elements
LED for status indication per input n n
LED for status indication per output n n n
LED for operation/status display n n n
Pushbuttons for local operation on the device n n n
Power supply
Electronics powered via an integrated power supply unit for
supply voltage 230 V AC
n n n
Bus-powered electronics n n n n n n
Bus-dependent operation possible n n
2)
n
Bus connection
Integrated bus coupling units n n n n n n n n n
Bus connection via bus terminal n n n n n n n n n
Bus connection via contact system to data rail n n
Outputs
Load output
Floating relay contact 8
3)
1 2 1 1
Silent semiconductor switch 6
Electrically interlocked relays (for reversing direction of rotation) 4
Load types
Rated contact voltage, AC [V] 230 230 230 230 230 230 230
Rated contact current [A] 6 16 16 6 6
Max. short-time current 1.5
Switching capacity for permanent loading [W] 12
Protection
Electronic protection of outputs against overload and short circuit n n n
Universal inputs/outputs
Adjustable universal inputs/outputs
Inputs
Max. cable length, unshielded, twisted [m] 100 100 50 5 5 5 5 10 10
For signal input (floating contact) 2 x 3 2 2 2 2 2
4)5)
4
4)5)
Determination of switching state by means of the voltage generated in the
device
n n n n n n n
For voltage input AC/DC 12...230 V 8 8
PT1000 temperature sensor input
1)
For current application programs, see www.siemens.com/gamma-td
2)
Each input affects the output of the same name, adjustable as timer or impulse relay
3)
Except channel A
4)
The inputs are mutually insulated from the base
5)
Inputs, alternatively can be used as outputs for controlling LEDs up to a maximum of 2 mA