User Manual
2-18
Output devices
Binary output devices
Switching actuators / DIN rail mounted devices
Phase out
Siemens Switzerland Ltd
Building Technologies Division
2019www.siemens.com/gamma
2
Stock No. Product No. DT
5WG1511-1AB02 N 511/02 A
N 511/02 Switching actuator, 8 x AC 230 V, 16 A
• One relay contact per output as switching element
• Rated operating voltage of relay contact: 230 V AC
• Rated current of relay contact: 16 A, p.f. = 1
• Integrated power supply for the electronics, connected to 230 V AC
• Push button to switch between bus operation and direct operation
• Yellow LED to indicate direct operation activated
• 1 red LED per output to indicate the switching state
• One push button per output to switch the output via a toggling function in direct operation mode,
functional if 230 V AC present, (even if bus voltage absent or interrupted or bus communication not
yet activated)
• Selection whether outputs are to be congured identically or individually
• Operation mode selectable for each output (normal mode, time switch mode)
• Selectable switching behaviour for each output (NO contact/NC contact)
• Adjustable On and Off delay times
• Selectable logic operation (AND/OR) for two communication objects and variable start value of the
logic operation at bus voltage recovery
• Selectable additional night mode object for each output for time-limited switching on of the
illumination at night
• Adjustable On period for night or time switch operation mode
• Selectable warning signal prior to imminent switching-off by means of three-times short off and on
switching (ashing) at night or time switch operation mode
• Possibility to add one additional status indication object per output for status reporting
• Sending of status objects on request and/or automatically after a change
• Integrated 8-bit scene control and linking of each output into up to 8 scenes
• Unchanged switching state of all outputs if there is a power failur
• Adjustable switching state per output after mains voltage recovery
• Integrated bus coupling unit
• Bus connection both via bus terminal and contact system to a data rail
• Only half a standard bus load
• Rail-mounted device for mounting on rail TH 35 according to DIN EN 60715
Base function Only Switching
Rated voltage AC 230 V
Rated current 16 A
Number of channels 8
Switch-off warning Yes
Dimension width (1 MW = 18 mm) 8 MW
13-Switching actuators _ DIN rail mounted devices.indd 18 23.07.2018 14:09:02