User Manual
2-17
Output devices
Binary output devices
Switching actuators / DIN rail mounted devices
Phase out
Siemens Switzerland Ltd
Building Technologies Division
2019www.siemens.com/gamma
2
Range overview N567/..
Product Title Dimension width
(1 MW = 18 mm)
Stock No. Product No. DT
Switch actuator, 4 x 230 V AC, 8 A 4 MW 5WG1567-1AB01 N 567/01 A
Switch actuator, 8 x 230 V AC, 8 A 4 MW 5WG1567-1AB11 N 567/11 A
Switch actuator, 8 x 230 V AC, 2 A 4 MW 5WG1567-1AB12 N 567/12 A
Switch actuator, 16 x 230 V AC, 10 A 8 MW 5WG1567-1AB22 N 567/22 A
Switch actuator
• One potential-free relay contact per output channel
• Electronics powered via an integrated power supply unit for 230 V AC
• Pushbutton for switching between bus operation and local operation
• A yellow LED indicating local operation
• 1 red LED per output channel to indicate switch status
• One pushbutton per output channel to activate the output through a UM-function in local operating
mode
• Operational with an 230 V AC supply, (even with no bus voltage and faulty or not activated bus
communication)
• Choice between identical or individually parameterized outputs
• Operating mode selectable for each channel (normal operation, time switch operation)
• Adjustable switching on/off delay
• Selectable logic link (AND/OR) between two communication objects and presettable logic operator for
bus voltage return
• Possibility to add an additional night operation object per output channel for time limited activation of
output (lighting) at night
• Selectable warning signal prior to imminent switching off in form of three times short off/on switching
(ashing)
• Possibility to add one additional status indicator object per output channel, sending of status objects
on request and/or automatically after change
• Possibility to add additional object to drive the integrated 8-bit scene controller, integrated 8 bit scene
control and linking each output channel to up to 8 scenes
• Unchanged switch state for all output channels in case of power failure
• Selectable switch state after return of power for each output channel
• Integrated bus coupling units, bus connection via bus terminal or contact system to data rail, only 50%
of standard busload
• Modular installation devices for mounting on TH35 EN 60715 mounting rail
N 567/..