User Manual

2-13
Output devices
Binary output devices
Switching actuators / DIN rail mounted devices
Siemens Switzerland Ltd
Building Technologies Division
2019www.siemens.com/gamma
2
Switching actuator
One relay contact per output as switching element
Rated contact operating voltage AC 230 V
Rated contact frequency: 50/60 Hz
Per output with mechanical display of the switching status via slide switches, which can also be used
for direct manual operation of the switching output
Maintenance-free terminals for connection and through-wiring of untreated single-core, stranded or
multi-core conductors, 0.5 ... 2.5mm²
One phase terminal per output
Bus-powered electronics
Integrated bus coupling unit, bus connection via bus terminal block
Red LED for display of the activation of the addressing mode as well as the operational readiness
Housing: plastic, color RAL 7035 (light grey), N-system
DIN rail mounted device for mounting on rail TH35 according to DIN EN 60715
Type of protection: IP 20
Per output
selectable operating mode (normal mode, time switch mode, ashing mode)
selectable relay mode (NC/NO)
variable On and Off delay times
two selectable logic operations (AND, OR, NAND, NOR, XOR, FILTER, TRIGGER)
selectable sending of status objects on request, cyclically and/or automatically after a change
selectable switching state on bus voltage failure
selectable start value of the switching object on bus voltage recovery
optional addition of a night mode object for time-limited switching On of the output, i.e. the
illumination, at night
variable On period at night or time switch mode
selectable addition of an object to change the On period at night or time switch mode
selectable post-triggering (1x, 2x, 3x, 4x, 5x) of the On period in time switch mode
selectable warning signal prior to imminent switching-off by brief off and on switching (ashing) at
night or in time switch mode and/or via an optional warning object
Per output selectable functions:
For manual override ON
For permanent OFF switching
Blocking of the output
For switching on or off in forced mode
Counting of operating hours and threshold monitoring
Counting of load cycles and threshold monitoring
Integrated 8-bit scene control with up to 8 scenes per output
Construction site function switching
Object for monitoring of device function
Object for targeted retrieval of status values
N 53x/..