User Manual
2-11
Siemens Switzerland Ltd www.siemens.com/gamma 2019
Building Technologies Division
Output devices
Technical specications
Load data for switching actuators per channel
... Continuation of the table
Type
N 567/01
N 567/11
N 567/12
N 567/22
N 502/02
UP 510/03
UP 510/13
RS 510/23
JB 510C23
UP 511/10
UP 562/31
RL 512/23
JB 512C23
RL513D23
JB 513C23
Contact current
Rated current, AC [A] 8 8 2 10 16 10 16 6 16 AX 10
AC1 operation (p.f. = 0.8) [A]
1) 1) 1) 1) 1) 1) 1) 1) 1) 1)
AC3 operation (p.f. = 0.45) [VA] 500 500 200 500 500 500 500 500 3680 500
24 V DC (resistive load) [A] 8 8 2 10
1) 1) 1) 1) 1) 1)
Maximum switch-on peak current
• t = 150 s [A]
• t = 250 s [A]
• t = 600 s [A]
200
160
100
200
160
100
100
80
50
200
160
100
200
160
100
200
160
100
450
320
220
450
320
220
450
320
220
200
160
100
Contact voltage
Rated voltage, AC [V] 230 230 230 230 230 230 230 230 230 230
Service life
Mechanical service life
Switching operations in millions
2 10 20 30 30 10 2 2 1 10
Electrical service life
Switching operations in millions
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
Power loss
Maximum power loss per device at
rated power [W]
5 4 5 9 13 3 2 1 3 3
Switching capacities/load types, loads
Resistive load [W] 1840 1840 460 2300 3680 2300 3680 1380 3680 2300
Minimum switching capacity [V/mA] 5/100 24/10 5/10 24/100 24/100 24/10
1)
)
12/100 24/10
DC switching capacity [VA] 24/8 30/8 24/8 24/10 24/16 30/10
1) 1)
24/16 30/10
Maximum capacitive load [F] 35 35 12 35 35 35 105 105 200 35
Incandescent lamps
Incandescent lamps [W] 1000 1000 500 1000 1000 1000 2500 1380 3680 1000
Halogen lamp 230 V [W] 1000 1000 500 1000 1000 1000 2200 1380 3680 1000
LV halogen lamp with conventional
transformer (inductive) [VA]
200 ...
500
200 ...
500
200 500 500
200 ...
500
1000 1000 2000
200 ...
500
T5/T8 fluorescent lamps
Uncorrected [VA] 500 500 200 500 500 500 28 x 58 1380 3680 500
Parallel corrected
(at max. possible C) [W]
2 x 58 2 x 58
200
(12 F)
2 x 58 2 x 58 2 x 58 15 x 58 15 x 58 2500 2 x 58
DUO circuit [VA] 1000 1000
200
(12 F)
1000 1000 1000 28 x 58 1380 3680 1000
Compact lamps
Uncorrected [VA] 500 500 200 500 500 500
1) 1)
3680 500
Parallel corrected
(at max. possible C) [W]
300
(35 F)
300
(35 F)
200
(12 F)
300
(35 F)
300
(35 F)
300
(35 F)
1) 1)
2500 300
1)
On request
2)
The number of ECG types takes into account the use of miniature circuit breakers with characteristic B
For complete technical specifications, see: www.siemens.com/gamma-td
22