User Manual
e1851a
14
Siemens Building Technologies
Cerberus Division
01.2002
Details on the planning of the fire detection systems
Clean room on 2
nd
floor
Length
55m
Width 50m
Area 2750m
2
Height 3.4m
High sensitivity air sampling smoke detection system with HSD detectors in a 2m high
raised floor:
– 6 or 12 BDH 2450.1 detection devices with interface card BDC2400 (pre-alarm 15%,
Alarm 30%)
– 6 AD2 active detectors
Air sampling tubes:
– 2 air sampling tubes mounted parallel in 2 metre high raised floor; first tube 1.25m above
the floor, second tube 1.85m above the floor, both in front of the aspiration filters of the air
circulation fans.
Air sampling holes:
– Holes every 60cm (see planning guidelines)
Response sensitivity:
– The system reacts to a test fire with 5 metal film resistors 10Ω 0.6W connected in parallel
at 9V max. 5A.
Utilities distribution area, 1
st
floor
Length
55m
Width 60m
Area 3300m
2
Height 3.4m
Ventilation: minimal (< 0.1 m/s)
Point-type smoke detectors:
– Type DO1151 with APS007S parameter set (1 detector every 25m@)
– Type DO1101 Ex for various explosion-hazard areas
Suitable test fire:
– SG3000 smoke generator
Air treatment floor, 3
rd
floor
Length
55m
Width 60m
Area 3300m
2
Height 3.4m
Size: 55m x 60m = 3300m
2
Ventilation:
– Depending on location between <0.1m/s and < 0.5m/s
Point-type smoke detectors:
– Type DO1151 with APS007S parameter set (1 detector every 50m
2
)
Suitable test fire:
– SG3000 smoke generator