1 Memory map
To provide compatibility with ETS the operating system does a memory translation from bus
addresses to the internal addresses of the microcontroller. That means that for example the
start of the address table for the ETS is 0x0116 and in reality it is 0x8116 in the
microcontroller.
The following memory map tables show respectively the real memory addresses in the
microcontroller, the addresses which are used on the bus to access them, the type and for
what they are used.
1.1 BIM M 130, BIM M 135 and Chipset 184/01
Address
in F0534
Bus
access
address
Used by
Type
0xFEDF
0xFBD0
n.a.
System
RAM
0xFBCF
0xFB00
n.a.
User
(Stack and Variables)
RAM
0xF7FF
0xF400
n.a.
System
RAM
0xBFFF
0xA000
n.a.
System
(Reserved)
Flash
0x9FFF
0x8116
0x1FFF
0x0116
User
(Appl.-Code)
Flash
0x8115
0x8000
0xE915
0xE800
User
(Appl.-InfoBlock)
Flash
0x7FFF
0x7800
0xE7FF
0xE000
User
(RootCode)
Flash
0x77FF
0x7700
n.a.
System
(JumpTable)
Flash
0x76FF
0x0000
n.a.
System
Flash