User Manual
29
Siemens Building Technologies
Cerberus Division
e1143b
06.2000
4.3 Analog points
The analog point representation will be implemented in future versions of LMSmodular.
4.4 Command representation
The following table presents the list of CMX commands (telegram description and
meaning) supported by the FHI Pad. Commands are transmitted to the FHI Pad in
CDSF.
Command
number.
I/O
type
Address
number
Par.
01
Par.
02
Par.
03
Par.
04
Par.
05
Done
Ope.
Done
Auto
Description
00 0 add 0 0 0 0 0 no yes Unit Status req.
00 0 add 1 val0 val1 val2 0 yes yes Modify date-time
01 Reserved
02 Reserved
03 0 add # pnt 0 0 0 0 yes no Deact. dig.manual
04 0 add # pnt 0 0 0 0 yes no Activ. dig.manual
05 Reserved
06 Reserved
07 Reserved
08 Reserved
09 Reserved
10 Reserved
11 0 add # pnt 0 0 0 0 yes no Set to auto
12 Reserved
13 0 add # pnt 0 0 0 0 yes no Ack dig. block
14 1 add # pnt 0 0 0 0 yes no Ack ana. block
15 0 add # pnt 0 0 0 0 yes no Reset dig. block
16 1 add # pnt 0 0 0 0 yes no Reset ana. block
17 1 add # pnt val. val. 0 0 yes no Modify analog
add (Cluster) local address: range 00H-13H.
valx where x could be 0, 1 or 2. They are the values of data-time.
pnt number of pointer; range is 3-24.
val analog value (IEEE format is used).
I/O type type of I/O involved
0 = digital command.
1 = analog command.
Ope command should be issued by the operator.
Auto command should be issued by LMS automatically.
In the first version, analog blocks are not yet treated.
Standard command LMS level FSS level
0 80H 80H
1-2 Local address 0000H
3-4 command number command number
5-6
point number (1
st
parameter)
block number
7-8
2
nd
parameter
parameter number (group number)
9-10
11-12
13-14
byte
15