User Manual

26
Siemens Building Technologies
Cerberus Division
e1143b
06.2000
3.5 Security/safety commands treatment.
The integrated system manages the following commands
- CZ10 reset command
- CZ10 acknowledge command
- CZ10 night switch-over
- CZ10 day switch-over
- include a CZ10 fire group
- exclude a CZ10 fire group
- include a CZ10 technical group
- exclude a CZ10 technical group
- set on a CZ10 technical output
- set off a CZ10 technical output
- CS11 reset command
- CS11 acknowledge command
- CS11 night switch over
- CS11 day switch over
- set on a CS11 control element
- set off a CS11 control element
- include a CS11 zone
- exclude a CS11 zone
- CZ12 reset command
- CZ12 acknowledge command
- CZ12 night switch-over
- CZ12 day switch-over
- CZ12 include group
- CZ12 exclude group
- CC60 reset command
- CC60 acknowledge command
- CC60 night switch over
- CC60 day switch over
- include CC60 gas detector
- exclude CC60 gas detector
- set on a CC60 technical output
- set off a CC60 technical output
The FSS issues these commands as Standard Protocol Commands, according to the
following format:
Standard command FSS level
0 80H
1-2 0000H
3-4 command number
5-6 block number
7-8 parameter number (group number)
9-10 0000H
11-12 0000H
13-14 0000H
byte
15 00H
If the command is a global one (e.g. acknowledge) the FSS must specify any block
number that belongs to the control panel. The FSS system manager that configures the
package should take care of it.