User Manual

23
Siemens Building Technologies
Cerberus Division
e1143b
06.2000
In order to discriminate the range for the Zones, the following rule applies to the two
identification data block field (1 and 2):
Identification data block Zona range
0401-04FA 1-250
0501-05FA 251-500
0601-06FA 501-750
0701-07FA 751-1000
Identification data block Zona range
0801-08FA 1-250
0901-09FA 251-500
0A01-0AFA 501-750
0B01-0BFA 751-1000
Identification data block Zona range
0C01-0CFA 1-250
0D01-0DFA 251-500
0E01-0EFA 501-750
0F01-0FFA 751-1000
The ranges are defined up to 1000 zones (although the real treatment regards 512
zones only).
For Zones, Section, Time program, ZoneLock and ZoneMasking the following corre-
spondences are valid:
LMS point number iten range
15-110 Zones 1-96
121-184 Section 1-64
187-194 Time program 1-8
221-316 ZoneLock 1-96
358-389 Zone 97-128
390-421 ZoneLock 97-198
422 Time program 9
423-457 Section 65-99
459-584 Zone 129-254
585-710 ZoneLock 129-254
714-715 Zone 255-256
716-717 ZoneLock 255-256
718-973 ZoneMas 1-256
974-1229 Zone 257-512
1230-1485 ZoneLock 257-512
1486-1741 ZoneMas 257-512
3.2.6 CZ12, CS4, CS4-40 supported commands
The following table presents all of the CZ12, CS4, and CS4-40 commands available.
Commands do not require any configuration on FSS.
Command description Command number Command parameter
Status request 0 block #
Reset* 2 block # (*)
Acknowledgement 1 block #
Night switch over 29 block #
Day switch over 30 block #
Include group 24 block #
Exclude group 25 block #
Command number
It is the relative command number for CZ12, CS4 and CS4-40 (Please refer to
LMSmodular Configuration Reference for a complete command list).