For CS4 version 6a , the pad version 5.25 supports the subtypes 3 and the following
points with the related messages:
Point number Point description Status Block value Treatment flag
normal 5 0
excluded 4 1
test 3 1
no ready 2 2
sabotage 0 2
al. + sab. 1 2
testalarm 6 2
358-389
#128
Addresses [zones]
alarm 7 2
normal 5 0390-421
#128
Address [zone] lock
on 4 1
For CS4 version 7, the pad version 5.25 supports the subtypes 3 and the following
points with the related messages:
Point number Point description Status Block value Treatment flag
normal 5 0
excluded 4 1
test 3 1
no ready 2 2
sabotage 0 2
al. + sab. 1 2
testalarm 6 2
459-584
#254
Addresses [zones]
alarm 7 2
normal 5 0423-457
#99
Group [section]
excluded 4 1
on 4 2422
#9
Time program
off 5 0
normal 5 0585-710
#254
Address [zone] lock
on 4 1
For CS4-40 version 6a, 7, and 8, the pad version 5.25 supports the subtypes 4 and 5
and the following points with the related messages:
Point number Point description Status Block value Treatment flag
normal 5 0
excluded 4 1
test 3 1
no ready 2 2
sabotage 0 2
al. + sab. 1 2
testalarm 6 2
714-715
974-1229
#512
addresses [zones]
alarm 7 2
normal 5 0716-717
1230-1485
#512
address [zone] lock supervision
on 4 1
normal 5 0
fault 0 2
713 ct411 power supply
battery 1 2
normal 5 0718-973
1486-1741
#512
address [zone] masking
temper 7 1
For each CZ12, CS4 and CS4-40 only the required blocks must be configured.
The zones become up to 512 according to the LMSmodular CS4-40 point list, the CS4-
40 control unit requires two new control unit subtypes: 4 and 5.