According to the LMS organisation, the CZ12, CS4 and CS4-40 are managed with the
following subsystem subtype:
§ 0 CZ12 with Cerban protocol (decimal, 96 zones)
§ 1 CZ12 V5 with Cerban protocol (decimal, 96 lock zones)
§ 2 CS4 V6 with Cerban protocol (decimal, 50 users)
§ 3 CS4 V6a and v7 with Cerban/hex protocol
(hexadecimal, 128 zones and lock zones)
§ 4 CS4-40 V6a with Cerban/hex protocol
(hexadecimal, 254 zones, lock zones, masking zones)
§ 5 CS4-40 V7 and V8 with Cerban/hex protocol
(hexadecimal, 512 zones, lock zones, masking zones)
For CZ12 version 5 and CS4 version 6, the pad version 5.20 supports the following
points with the related messages:
Point number Point description Status Block value Treatment flag
normal 5 0
fault 0 2
1 Gateway_link_status
fault net 2 2
normal 5 04 General_fault
fault 0 2
normal 5 0
fault 0 2
5 Power_fault
battery 7 2
off 5 0
on 1 1
6 Fault_xmit
delay 2 1
normal 5 0
on 4 1
7 Intrusion_alarm_tx
delay 6 1
normal 5 0
excluded 4 1
115 Line_sabotage
sabotage 0 2
normal 5 0
excluded 4 1
116 Panel_sabotage
sabotage 0 2
night 5 0
day 4 0
119 Organisation
no ready 1 1
normal 5 0117 Part_off
excluded 1 1
normal 5 0
excluded 4 1
test 3 1
no ready 2 2
sabotage 0 2
al.+ sab 1 2
testalarm 6 2
15-110
#96
Addresses [zones]
alarm 7 2
normal 5 0121-184
#64
Groups [sections]
excluded 4 1
normal 5 0111 Duress_Alarm
alarm 4 2
on 4 2187-194
#8
Time_Program
off 5 0
normal 5 0221-316
#96
Address_lock [zones]
on 4 1