User Manual

20
Siemens Building Technologies
Cerberus Division
e1143b
06.2000
3.2.4 CS-11 supported commands
The following table presents all CS11 commands available to an FSS user. Commands
do not require any configuration on the FSS.
Command Description Command number Command parameter
Status request 0 block #
General reset 2 block # (*)
General acknowledge 1 block #
Section acknowledge 1 block #
Section reset 2 block #
Exclude all zones of a section 40 block #
Include all zones of a section 41 block #
Night switch over 21 block #
Day switch over 22 block #
Control element on 52 block #
Control element off 53 block #
Exclude zone 40 block #
Include zone 41 Block #
Command number
It is the relative command number for CS11 (Please refer to LMSmodular Configura-
tion Manual for a complete command list).
Command parameter
It is a mandatory command parameter. It is the block number which corresponds to
the involved ADF number.
(*) This general command requires (as parameter) one of the block numbers (any)
which belongs to the control unit.
At FSS level you must not use an automatic acknowledge command, because this for-
bids the remote transmission alarm on CS11, a condition that could be potentially dan-
gerous.
3.2.5 CZ12, CS4, CS4-40 points representation
The following table presents the CZ12, CS4 and CS4-40 image in terms of FSS blocks
and the specific values representing the different states.
Block value
It is the value that the block assumes when it is in the status listed on the corre-
sponding column.
All integer values have been chosen in order to be processed by the FSS. The FSS
template recognises all individual integer values in the range 0-8.
Status
It is the description of the state for security points representation. All the statuses not
explicitly mentioned are not treated at all.
Treatment flag
It specifies the treatment flag used in the Standard Protocol Messages