3.2.1 CZ10 points representation
The following table presents the CZ10 image in terms of FSS blocks and the specific
values representing the different states.
Point number Point description Status Block value Treatment flag
normal 5 0
fault 0 2
1 Gateway_link_status
net fault 2 2
normal 5 03 General_fault
fault 0 2
normal 5 0
fault 0 2
5 Power_fault
battery 7 2
off 5 06 Fault_xmit
on 4 1
off 5 07 Fire_alarm_xmit
on 4 1
normal 5 0
loc.al. 6 2
8 Fire_alarm
gen.al. 7 2
night 5 010 Fire_organization
day 4 0
normal 5 011 Fire_part_off
exclud. 6 1
normal 5 0
exclud. 4 1
fault 0 2
test 3 1
alarm 7 2
16-111 Fire\Tech_group
testalarm 6 2
normal 5 0
active 6 2
264-1463 Line_elements
fault 2 2
off 5 0168-263 Technical_digital_outputs
on 6 2
Block value
This is the value that the block assumes when it is in the status listed in the corre-
sponding column.
All integer values have been chosen in order to be processed by the FSS. The FSS
template recognises all individual integer values in the range 0-8.
Status
It is the description of the state for security points representation. All the statuses not
explicitly mentioned are not treated at all.
Treatment flag
It specifies the treatment flag used in the Standard Protocol Messages.
For each CZ10, only those blocks which are required must be configured.